Products · Dry coolers产品 · 干冷器

Can a dry cooler make the 41 °C facility water of NVIDIA's reference example?干冷器能造出 NVIDIA 参考示例中 41 °C 的设施水吗?

Over 3 years, warm water widens the dry cooler's role in AI plants.未来三年,温水让干冷器在 AI 冷站中的作用更大。

Data as of 2026-10-13, reviewed monthly.数据截至 2026-10-13,每月复核。Condition: ratings at the warm-water point, and climate or adiabatic assist前提:按温水工况公布额定值,并满足气候条件或接受绝热辅助

Interactive figure with its parts named. Requires JavaScript.互动图,标有各部件名称。需启用 JavaScript。

Cooled fluid leaving冷却后流出的液体Hot fluid from the plant来自冷站的高温液体Drawn from BAC's public documents; not an engineering drawing.依据 BAC 公开资料绘制,并非工程图。

Inside a double-stack dry cooler双层干冷器的内部

How it works, and the sources工作原理和来源

Hot fluid from the plant enters the coils at one end of the unit, runs through copper tubes in aluminium fins, and leaves cooler at the same end. Four axial fans on top draw outdoor air in through the upright coils on both long sides and blow it out upward; BAC describes the unit as counter flow, axial fan, induced draft. This dry version has no compressor and no water spray, so the leaving fluid stays above the outdoor air temperature. The two coil tiers, eight panels per tier, belt drives, walkways, door, external platform, control panel and VFDs follow BAC's public TDFS brochure, parts map, rigging manual and guide specification. The overall length, width and height follow the published 38 ft 1 in, 11 ft 7 in and 19 ft 7 in. The high inlet and low outlet on each tier, the field headers, the coil thickness, the brace positions, the motor base and the side of the shaft it sits on, and the blade count and shape are illustrative. The far-side coils have their own connections, hidden behind the unit, and field piping joins both sides. The motor-removal davit, the optional hail guards and the platform toeboards are not drawn. BAC did not review this figure. Six of the 19 product lines in this page's table list V-shape coils instead.来自冷站的高温液体从机组一端进入盘管,流过铝翅片中的铜管,冷却后从同一端流出。顶部四台轴流风机把室外空气从两条长边的直立盘管抽入,再向上排出;BAC 把这款机组描述为逆流、轴流风机、引风式。这款干式机组没有压缩机,也不喷水,因此出液温度始终高于室外气温。上下两层盘管、每层八块盘管、皮带传动、走道、检修门、外部平台、控制柜和变频器均依据 BAC 公开的 TDFS 样本、零件图、吊装手册和招标规范绘制。总长、总宽和总高采用公布的 38 英尺 1 英寸、11 英尺 7 英寸和 19 英尺 7 英寸。每层的上进下出布置、现场集管、盘管厚度、斜撑位置、电机底座及其在风机轴哪一侧,以及叶片数量和形状均为示意。远侧盘管有各自的接口,被机组挡住,由现场管道把两侧连接起来。电机吊装架、可选的防冰雹网和平台踢脚板未画出。本图未经 BAC 审阅。本页表格的 19 个系列中,有 6 个标明采用 V 形盘管。 BAC TDFS brochureBAC TDFS 样本 · BAC rigging and assembly manualBAC 吊装和组装手册 · BAC parts mapBAC 零件图 · BAC guide specificationBAC 招标规范 · BAC Europe product pageBAC 欧洲产品页

What the catalogues state: 19 dry and adiabatic lines样本里写了什么:19 个干式与绝热系列
Capacity tied to fluid and air temperatures容量与液温和气温挂钩 3 of 1919 个中 3 个Capacity or range without conditions只有容量或范围,没有工况 14 of 1919 个中 14 个No capacity stated未写容量 2 of 1919 个中 2 个
Capacity tied to容量与液温和 3 of 1919 个中 3 个Capacity or range只有容量或范 14 of 1919 个中 14 个No capacity stated未写容量 2 of 1919 个中 2 个

Dry coolers are sized in vendor selection software; a catalogue kilowatt without fluid and air temperatures cannot be compared. None of the three rated points is a complete single-unit rating.干冷器通过厂商选型软件配置;没有液温和气温的样本千瓦数无法比较。三个有工况的点都不是完整的单机额定值。

What the catalogues state: 19 dry and adiabatic lines样本里写了什么:19 个干式与绝热系列

Table表格

Line系列What the catalogue states样本写了什么Source来源
Alfa Laval Cooling PodCapacity or range without conditions只有容量或范围,没有工况link链接
Baltimore Aircoil (BAC) Trillium TRFS adiabatic coolerNo capacity stated未写容量link链接
Baltimore Aircoil (BAC) TrilliumSeries TDFSCapacity tied to fluid and air temperatures容量与液温和气温挂钩link链接
Carrier 09VECapacity or range without conditions只有容量或范围,没有工况link链接
EVAPCO eco-Air EAW-DA Double StackCapacity or range without conditions只有容量或范围,没有工况link链接
EVAPCO eco-Air EAW-HD APEXCapacity or range without conditions只有容量或范围,没有工况link链接
Güntner High Density with hydroBLUCapacity or range without conditions只有容量或范围,没有工况link链接
Güntner V-shape VARIO (GFD / GFW)Capacity or range without conditions只有容量或范围,没有工况link链接
Kelvion Mega-Bay / Giga-BayCapacity or range without conditions只有容量或范围,没有工况link链接
Kelvion V-shape dry cooler (LV)Capacity tied to fluid and air temperatures容量与液温和气温挂钩link链接
LU-VE Alfa V Mega VXX3Capacity or range without conditions只有容量或范围,没有工况link链接
LU-VE Alfa V Mega VXX3 WETWALLCapacity or range without conditions只有容量或范围,没有工况link链接
Modine ECO dry coolers, adiabatic configurationsNo capacity stated未写容量link链接
Modine ECO Vshape-WCapacity or range without conditions只有容量或范围,没有工况link链接
Munters DGV V-shape dry coolerCapacity or range without conditions只有容量或范围,没有工况link链接
Munters DMI with INTELLIBATICCapacity or range without conditions只有容量或范围,没有工况link链接
Shenling Data-center evaporative dry cooler (数据中心蒸发冷却干冷器)Capacity or range without conditions只有容量或范围,没有工况link链接
Trane Dry-cooler offering (Europe)Capacity or range without conditions只有容量或范围,没有工况link链接
Vertiv Liebert direct-drive drycoolerCapacity tied to fluid and air temperatures容量与液温和气温挂钩link链接

Sources来源

  1. Vertiv Liebert direct-drive drycoolerVertiv Liebert direct-drive drycooler
  2. Trane Dry-cooler offering (Europe)Trane Dry-cooler offering (Europe)
  3. Carrier 09VECarrier 09VE
  4. Modine ECO Vshape-WModine ECO Vshape-W
  5. Munters DGV V-shape dry coolerMunters DGV V-shape dry cooler
  6. Güntner V-shape VARIO (GFD / GFW)Güntner V-shape VARIO (GFD / GFW)
  7. Kelvion Mega-Bay / Giga-BayKelvion Mega-Bay / Giga-Bay
  8. Kelvion V-shape dry cooler (LV)Kelvion V-shape dry cooler (LV)
  9. LU-VE Alfa V Mega VXX3LU-VE Alfa V Mega VXX3
  10. EVAPCO eco-Air EAW-HD APEXEVAPCO eco-Air EAW-HD APEX
  11. Baltimore Aircoil (BAC) TrilliumSeries TDFSBaltimore Aircoil (BAC) TrilliumSeries TDFS
  12. Alfa Laval Cooling PodAlfa Laval Cooling Pod
  13. Modine ECO dry coolers, adiabatic configurationsModine ECO dry coolers, adiabatic configurations
  14. Munters DMI with INTELLIBATICMunters DMI with INTELLIBATIC
  15. Shenling Data-center evaporative dry cooler (数据中心蒸发冷却干冷器)Shenling Data-center evaporative dry cooler (数据中心蒸发冷却干冷器)
  16. Güntner High Density with hydroBLUGüntner High Density with hydroBLU
  17. LU-VE Alfa V Mega VXX3 WETWALLLU-VE Alfa V Mega VXX3 WETWALL
  18. EVAPCO eco-Air EAW-DA Double StackEVAPCO eco-Air EAW-DA Double Stack
  19. Baltimore Aircoil (BAC) Trillium TRFS adiabatic coolerBaltimore Aircoil (BAC) Trillium TRFS adiabatic cooler
3of 19

Lines that tie a capacity to fluid and air temperatures把容量与液温和气温挂钩的系列

Catalogues and datasheets样本和数据表Full matrix完整矩阵
31–35.4°C

Air at or below which the two points with a leaving temperature could still make 41 °C water: Kelvion 31 °C (approach 10 K), Baltimore Aircoil (BAC) 35.4 °C (approach 5.6 K)两个写明出液温度的点,在不高于此气温时仍可造出 41 °C 的水:Kelvion 31 °C(接近温差 10 K),Baltimore Aircoil (BAC) 35.4 °C(接近温差 5.6 K)

Same approach assumed; a screen, not a rating假设接近温差不变;只是筛查,不是额定值Direct feed to the CDUs assumed假设直接给 CDU 供水KelvionKelvion Baltimore Aircoil (BAC)Baltimore Aircoil (BAC)
1,000+

Dry coolers in Kelvion's announced contract: more than USD 800 million, for 5 GW of project heat-rejection capacity in 2027Kelvion 公布的合同中的干冷器台数:超过 8 亿美元,用于 2027 年 5 GW 的项目排热能力

Company announcement公司公告KelvionKelvion

Judgement判断

Over the next three years warm water widens the dry cooler's role in the AI plant, alongside the chiller rather than in its place.

未来三年,温水让干冷器在 AI 冷站中的作用更大,但它与冷水机组互补,而不是取代冷水机组。

Judgement by LC. Sources: LC 的判断。来源:[1] [2] [3]

With 41–45 °C liquid cooling, the dry cooler can reject the plant's heat to outdoor air without a compressor whenever the air is cool enough; the chiller covers the rest.在 41–45 °C 液冷下,只要室外空气足够凉,干冷器不用压缩机就能把冷站的热量排到室外;其余时段由冷水机组承担。

Can a dry cooler make 41 °C water? The engineering reading干冷器能造出 41 °C 的水吗?工程解读

NVIDIA's reference example supplies 41 °C facility water to the CDUs. A dry cooler's leaving fluid sits a few kelvin above the outdoor air (its approach). Engineering reading, not a vendor statement: from each rated point, the air temperature at which that unit could still deliver 41 °C water at the same approach. Approach changes with flow, fan speed and selection, so this is a screen, not a rating. The reading assumes the dry cooler feeds the CDUs directly; with an intermediate heat exchanger, subtract that exchanger's approach as well.NVIDIA 的参考示例给 CDU 供 41 °C 的设施水。干冷器的出液温度比室外空气高几 K(接近温差)。以下是工程解读,不是厂商声明:按每个额定点,估算在相同接近温差下仍能供 41 °C 水的空气温度。接近温差随流量、风机转速和选型而变,因此这只是筛查,不是额定值。该解读假设干冷器直接给 CDU 供水;如有中间换热器,还要再减去该换热器的接近温差。 NVIDIA sourceNVIDIA 来源

Stated point (vendor source)标称工况点(厂商来源)kWEngineering reading工程解读
Vertiv Liebert direct-drive drycooler275leaving fluid not stated; approach cannot be read未写出液温度,无法读出接近温差
Kelvion V-shape dry cooler (LV)range 6–2,140范围 6–2,140leaves 35 °C at 25 °C air (approach 10 K): 41 °C water needs air at or below about 31 °C在 25 °C 空气下出液 35 °C(接近温差 10 K):要得到 41 °C 的水,空气约需不高于 31 °C
Baltimore Aircoil (BAC) TrilliumSeries TDFSup to (nominal family maximum) 最高(系列名义最大值) 2,931leaves 40.6 °C at 35 °C air (approach 5.6 K): 41 °C water needs air at or below about 35.4 °C在 35 °C 空气下出液 40.6 °C(接近温差 5.6 K):要得到 41 °C 的水,空气约需不高于 35.4 °C

How many hours a year the air stays below these lines, by city: 各城市一年有多少小时气温低于这些线:Countries, hours a dry cooler alone can make the water国家地区页:仅靠干冷器即可制水的小时数.。

What makers have said is coming厂商已宣布的下一步

through 20272027 年全年

Kelvion supplies more than 1,000 Mega-Bay dry coolers under that contractKelvion 按该合同供应 1,000 台以上 Mega-Bay 干冷器

Planned计划, announced 2026-10,2026-10 公布 source来源

Each stays a plan until a source confirms it happened. Passing the window does not prove shipment.在有来源确认发生之前,各项都只是计划。时间窗口过去并不代表已经出货。

Go deeper继续深入

Compare two or three自选两到三款比较

○ = not stated by the vendor. Values keep the vendor's own conditions; they are not a ranking. Choose "—" in the third box to compare two.○ = 厂商未标称。数值保留厂商自己的工况,不构成排名。第三个框选"—"即可只比较两款。

The three lines with stated conditions三个写明工况的系列3

Rule: every line that ties a capacity to fluid and air temperatures.规则:把容量与液温和气温挂钩的全部系列。

Vertiv Liebert direct-drive drycooler

275 kW; fluid 48.9 / — °C at 35 °C air.275 kW;进 / 出液 48.9 / — °C,空气 35 °C。

Largest standard 60 Hz model; 'Capacity shown is Drycooler THR at sea level'. Leaving fluid temperature not stated. 50 Hz: 242 kW.最大的 60 Hz 标准型号;“容量为海平面处干冷器总排热量”。未写出水温度。50 Hz 时为 242 kW。

Dry干式

Kelvion V-shape dry cooler (LV)

family 6–2,140 kW; fluid 40 / 35 °C at 25 °C air.系列 6–2,140 kW;进 / 出液 40 / 35 °C,空气 25 °C。

Capacity range 6–2,140 kW printed with its conditions directly beneath it: water, tA1 = 25 °C air, tL1 = 40 °C in, tL2 = 35 °C out. A conditioned family range, not one unit's rating.容量范围 6–2,140 kW,下方直接印有工况:水,tA1 = 25 °C 空气,tL1 = 40 °C 进液,tL2 = 35 °C 出液。这是带工况的系列范围,不是单台额定值。

Dry干式

Baltimore Aircoil (BAC) TrilliumSeries TDFS

up to (nominal family maximum) 2,931 kW; fluid 46.1 / 40.6 °C at 35 °C air.最高(系列名义最大值) 2,931 kW;进 / 出液 46.1 / 40.6 °C,空气 35 °C。

'Nominal capacity based on a 115° F EWT and 105° F LWT at a 95° F dry bulb'. The brochure does not say which model reaches 10,000 MBH.“名义容量基于 115°F 进水、105°F 出水、95°F 干球温度”。样本没有说明哪个型号达到 10,000 MBH。

Dry干式
The latest four product, contract and rule events最近四项产品、合同与法规事件4
  • BAC launches the TrilliumSeries dry coolerBAC 发布 TrilliumSeries 干冷器 Dry and adiabatic coolers for data centers面向数据中心的干冷器与绝热冷却器 source来源
  • Kelvion updates its adiabatic spray system: ambient-responsive water control and a VFD pump as standardKelvion 更新绝热喷淋系统:随环境调节用水,标配变频水泵 Dry and adiabatic coolers for data centers面向数据中心的干冷器与绝热冷却器 source来源
  • EVAPCO introduces the CTI-certified eco-Air APEX dry cooler for high-density data centersEVAPCO 推出面向高密度数据中心、经 CTI 认证的 eco-Air APEX 干冷器 Dry and adiabatic coolers for data centers面向数据中心的干冷器与绝热冷却器 source来源
  • Kelvion announces an AI data-center heat-rejection contract worth more than USD 800 million, for 5 GW of project capacityKelvion 宣布一份 AI 数据中心排热合同,金额超过 8 亿美元,对应 5 GW 项目排热容量 Contracts and ownership订单与收购 source来源

A date marks an event that happened; the plans are shown above with their windows. The full six-year roadmap is in the next rows.有日期的是已发生的事件;计划及其时间窗口见上文。完整六年路线图在下面。

Company news: acquisitions, factories and funding公司动态:收购、工厂和融资7 of 87 / 8
  • LU-VE's expanded Tianmen plant in China becomes operational: from 19,000 to over 43,000 m²LU-VE 扩建后的中国天门工厂投产:从 19,000 平方米扩大到 43,000 平方米以上 Factories工厂 source来源
  • Munters breaks ground on its Daleville, Virginia expansion for data-center cooling production (chillers)Munters 在弗吉尼亚州 Daleville 动工扩建数据中心冷却产品生产(冷水机组) Factories工厂 source来源
  • LU-VE reports that production of large GIANTS EHDV dry coolers has started at TianmenLU-VE 报告天门工厂已开始生产大型 GIANTS EHDV 干冷器 Factories工厂 source来源
  • LU-VE inaugurates 20,000 m² of new production area in Jacksonville, TexasLU-VE 在得克萨斯州杰克逊维尔启用 20,000 平方米新生产区 Factories工厂 source来源
  • SLB agrees to acquire 100% of Kelvion: USD 4.1 billion enterprise valueSLB 同意收购 Kelvion 100% 股权:企业价值 41 亿美元 Contracts and ownership订单与收购 source来源
  • Munters inaugurates the expanded Daleville campus (52,000 m²) and starts local chiller manufacturingMunters 启用扩建后的 Daleville 园区(52,000 平方米),开始本地生产冷水机组 Factories工厂 source来源
  • Planned计划 SLB's acquisition of Kelvion closes, subject to approvalsSLB 完成收购 Kelvion(须获批准) announced 2026-082026-08 公布 Contracts and ownership订单与收购 source来源

All of them are in the full roadmap.全部见完整路线图。

Full roadmap, makers and owners, and the method完整路线图、厂商与所有者、方法13 events13 个事件

Roadmap, 2023 Q4 – 2029 Q3路线图,2023 年第四季度至 2029 年第三季度

Dated events from official sources. Planned events show the window the source states; passing the window does not prove shipment. No future model is inferred.来自官方来源的有日期事件。计划事件显示来源给出的时间窗口;窗口过去并不代表已经出货。不推测未来型号。

Dry and adiabatic coolers for data centers面向数据中心的干冷器与绝热冷却器

  1. Jan 20252025 年 1 月 BAC launches the TrilliumSeries dry coolerBAC 发布 TrilliumSeries 干冷器
  2. Apr 20252025 年 4 月 Kelvion updates its adiabatic spray system: ambient-responsive water control and a VFD pump as standardKelvion 更新绝热喷淋系统:随环境调节用水,标配变频水泵
  3. Feb 20262026 年 2 月 EVAPCO introduces the CTI-certified eco-Air APEX dry cooler for high-density data centersEVAPCO 推出面向高密度数据中心、经 CTI 认证的 eco-Air APEX 干冷器

Contracts and ownership订单与收购

  1. Oct 20242024 年 10 月 Munters completes the Geoclima acquisitionMunters 完成收购 Geoclima
  2. Aug 20262026 年 8 月 SLB agrees to acquire 100% of Kelvion: USD 4.1 billion enterprise valueSLB 同意收购 Kelvion 100% 股权:企业价值 41 亿美元
  3. Oct 20262026 年 10 月 Kelvion announces an AI data-center heat-rejection contract worth more than USD 800 million, for 5 GW of project capacityKelvion 宣布一份 AI 数据中心排热合同,金额超过 8 亿美元,对应 5 GW 项目排热容量
  4. Target through 2027目标 2027 年全年 Kelvion supplies more than 1,000 Mega-Bay dry coolers under that contractKelvion 按该合同供应 1,000 台以上 Mega-Bay 干冷器 announced Oct 20262026 年 10 月公布 planned计划
  5. Target H1 2027目标 2027 年上半年 SLB's acquisition of Kelvion closes, subject to approvalsSLB 完成收购 Kelvion(须获批准) announced Aug 20262026 年 8 月公布 planned计划

Factories工厂

  1. Dec 20242024 年 12 月 LU-VE's expanded Tianmen plant in China becomes operational: from 19,000 to over 43,000 m²LU-VE 扩建后的中国天门工厂投产:从 19,000 平方米扩大到 43,000 平方米以上
  2. Jul 20252025 年 7 月 Munters breaks ground on its Daleville, Virginia expansion for data-center cooling production (chillers)Munters 在弗吉尼亚州 Daleville 动工扩建数据中心冷却产品生产(冷水机组)
  3. Jul 20252025 年 7 月 LU-VE reports that production of large GIANTS EHDV dry coolers has started at TianmenLU-VE 报告天门工厂已开始生产大型 GIANTS EHDV 干冷器
  4. May 20262026 年 5 月 LU-VE inaugurates 20,000 m² of new production area in Jacksonville, TexasLU-VE 在得克萨斯州杰克逊维尔启用 20,000 平方米新生产区
  5. Sep 20262026 年 9 月 Munters inaugurates the expanded Daleville campus (52,000 m²) and starts local chiller manufacturingMunters 启用扩建后的 Daleville 园区(52,000 平方米),开始本地生产冷水机组

Makers and owners厂商与所有者

Listed companies behind the products on this page: 本页产品背后的上市公司:CarrierCarrier, ModineModine, MuntersMunters, Shenling申菱环境, Trane TechnologiesTrane Technologies, VertivVertiv. Other makers: 其他厂商:Güntner (private非上市); Kelvion (private; SLB agreed to acquire it in 2026非上市;SLB 已于 2026 年同意收购); LU-VE (listed in Milan; not in this registry米兰上市;不在本名单中); EVAPCO (private非上市); Baltimore Aircoil (BAC) (part of Amsted Industries (private)Amsted Industries 旗下(非上市)); Alfa Laval (listed in Stockholm; not in this registry斯德哥尔摩上市;不在本名单中). See the value-chain map查看产业链地图 · Chillers deep dive冷水机组深度分析 · CDU deep diveCDU 深度分析

Method方法

Specifications come from each vendor’s datasheet, brochure or product page; each source was extracted by two different models and ruled against the saved text. Events come from vendor and buyer announcements; each was checked by script on the page and by an independent model. Evidence cut-off 2026-10-13. Personal research, not investment advice.规格来自各厂商的数据表、样本或产品页;每个来源由两个不同模型分别提取,并对照保存的原文裁定。事件来自厂商和收购方的公告,每条都经脚本在原页面核对并由独立模型复核。证据截止 2026-10-13。个人研究,不构成投资建议。

Database view: the full matrix, dry and adiabatic数据库视图:完整矩阵,干式与绝热19 rows19 行
Showing显示 19

Vendors state 70 of 171 displayed cells (a capacity range counts as stated). A value appears only where its conditions are stated; ranges are not ranked, and rows are sorted by company. °F is converted to °C and MBH to kW (1 MBH = 0.293 kW). ○ = not stated by the vendor (explained once here, not repeated in words in each cell).表中 171 个单元格里,厂商披露了 70 个(容量范围算作已披露)。数值只在写明工况时才放在工况列;范围不做排名,行按公司排序。°F 换算为 °C,MBH 换算为 kW(1 MBH = 0.293 kW)。○ = 厂商未标称(只在此说明一次,不在每格重复文字)。

Dry (12 lines)干式(12 个系列)

Company and line公司与产品Capacity kW容量 kWFluid in / out °C进 / 出液 °CAmbient at rating °C额定环境温度 °CRating fluid额定工况介质Fans (vendor wording)风机(厂商原文)Sound噪声Footprint L × W mm占地 长 × 宽 mmWater use (vendor wording)用水(厂商原文)Coil layout盘管布置Notes说明
Alfa Laval
Cooling Pod
family 500–1,000系列 500–1,000
“500 and 1000 kW*”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露2 or 3 fans, 60 in2 或 3 台风机,60 英寸not stated未披露6,066 × 2,438none (waterless)无(不用水)straight finned tube bundles直翅片管束'500 and 1000 kW* modular designs'; '*Actual heat transfer varies based on ambient conditions.'“500 和 1000 kW 模块化设计”;“实际换热量随环境条件变化”。
Baltimore Aircoil (BAC)
TrilliumSeries TDFS
up to (nominal family maximum) 最高(系列名义最大值) 2,931
“up to 10,000 MBH”
46.1 / 40.635not stated未披露4 fans, belt drive with VFD4 台风机,皮带传动,变频not stated未披露11,608 × 3,531none (dry only)无(纯干式)vertical coil立式盘管'Nominal capacity based on a 115° F EWT and 105° F LWT at a 95° F dry bulb'. The brochure does not say which model reaches 10,000 MBH.“名义容量基于 115°F 进水、105°F 出水、95°F 干球温度”。样本没有说明哪个型号达到 10,000 MBH。
Carrier
09VE
family 100–1,870系列 100–1,870
“100 to 1870 kW”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露6–20 fans, 800 / 910 mm, AC or EC6–20 台风机,800 / 910 mm,AC 或 ECnot stated未披露3,550–11,660 × 2,305–2,420 by model, without options按型号 3,550–11,660 × 2,305–2,420,不含选配optional spray misting可选喷雾not stated未披露Family range only; optional water misting into the air flow.只有系列容量范围;可选向进风喷雾。
EVAPCO
eco-Air EAW-HD APEX
family 2,655–3,367系列 2,655–3,367
“9,060 MBH to 11,490 MBH”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露belt-drive NEMA motors, VFD ready皮带传动 NEMA 电机,支持变频not stated未披露not stated未披露not stated未披露double stack双层叠放CTI-certified nominal range (CTI ATC-105DS) without conditions on the page.CTI 认证的名义容量范围(CTI ATC-105DS),页面未写工况。
Güntner
V-shape VARIO (GFD / GFW)
family 47–2,040系列 47–2,040
“GFD 75 - 2,040; GFW 47 - 740”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露up to 2 × 12 fans最多 2 × 12 台风机not stated未披露not stated未披露optional hydroBLU pads可选 hydroBLU 湿帘V-shapeV 型Range per type: GFD 75–2,040 kW, GFW 47–740 kW; hydroBLU pads optional.按类型给出范围:GFD 75–2,040 kW,GFW 47–740 kW;可选 hydroBLU 湿帘。
Kelvion
Mega-Bay / Giga-Bay
family 1,500–8,000系列 1,500–8,000
“1.5–4 MW (Mega-Bay), 4–8 MW (Giga-Bay) per module”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露Mega-Bay: 3 fans up to 14 ft; Giga-Bay: up to 22 ftMega-Bay:3 台最大 14 英尺;Giga-Bay:最大 22 英尺not stated未披露not stated未披露not stated未披露not stated未披露Per-module ranges without conditions: Mega-Bay 1.5–4 MW (three fans up to 14 ft), Giga-Bay 4–8 MW (fans up to 22 ft).每个模块的容量范围,未写工况:Mega-Bay 1.5–4 MW(三台最大 14 英尺风机),Giga-Bay 4–8 MW(最大 22 英尺风机)。
Kelvion
V-shape dry cooler (LV)
family 6–2,140系列 6–2,140
“6 kW - 2140 kW”
range printed with conditions范围附有工况
40 / 3525water水1–22 fans, 800–960 mm, AC or EC1–22 台风机,800–960 mm,AC 或 ECnot stated未披露largest type up to 13,200 × 2,503最大型号至 13,200 × 2,503optional adiabatic system可选绝热系统V-shapeV 型Capacity range 6–2,140 kW printed with its conditions directly beneath it: water, tA1 = 25 °C air, tL1 = 40 °C in, tL2 = 35 °C out. A conditioned family range, not one unit's rating.容量范围 6–2,140 kW,下方直接印有工况:水,tA1 = 25 °C 空气,tL1 = 40 °C 进液,tL2 = 35 °C 出液。这是带工况的系列范围,不是单台额定值。
LU-VE
Alfa V Mega VXX3
family 200–2,000系列 200–2,000
“200 to 2,000 kW (EN1048 standard)”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露AC or EC, 910 / 1,000 mmAC 或 EC,910 / 1,000 mmnot stated未披露not stated未披露not stated未披露V-shapeV 型Family range per EN 1048 without numerical rating temperatures.按 EN 1048 给出系列范围,未写额定温度。
Modine
ECO Vshape-W
family 100–2,000系列 100–2,000
“From 100 to 2000 kW”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露4–18 fan modules, 800 / 910 mm, AC or EC4–18 个风机模块,800 / 910 mm,AC 或 ECnot stated未披露not stated未披露not stated未披露V-shapeV 型Family range only.只有系列容量范围。
Munters
DGV V-shape dry cooler
family 140–1,680系列 140–1,680
“from 140 to 1680 kW”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露2–20 fans, 800 / 910 mm2–20 台风机,800 / 910 mmnot stated未披露not stated未披露not stated未披露V-shapeV 型Family range only.只有系列容量范围。
Trane
Dry-cooler offering (Europe)
family 250–500系列 250–500
“250 kW and 500 kW nominal duty”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露Nominal duties without rating conditions; units can be combined in multiples.名义容量,未写工况;可多台组合。
Vertiv
Liebert direct-drive drycooler
275
940
“938 MBH (275 kW)”
48.9 / —3540% ethylene glycol40% 乙二醇8 direct-drive propeller fans, ≤ 660 mm8 台直驱轴流风机,≤ 660 mm81.5 dB(A) at 1.5 m1.5 m 处 81.5 dB(A)4,356 × 2,213not stated未披露flat平置Largest standard 60 Hz model; 'Capacity shown is Drycooler THR at sea level'. Leaving fluid temperature not stated. 50 Hz: 242 kW.最大的 60 Hz 标准型号;“容量为海平面处干冷器总排热量”。未写出水温度。50 Hz 时为 242 kW。

Adiabatic or evaporative assist (7 lines)绝热或蒸发辅助(7 个系列)

Company and line公司与产品Capacity kW容量 kWFluid in / out °C进 / 出液 °CAmbient at rating °C额定环境温度 °CRating fluid额定工况介质Fans (vendor wording)风机(厂商原文)Sound噪声Footprint L × W mm占地 长 × 宽 mmWater use (vendor wording)用水(厂商原文)Coil layout盘管布置Notes说明
Baltimore Aircoil (BAC)
Trillium TRFS adiabatic cooler
not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露factory-installed wetted pads, used when needed工厂预装湿帘,按需启用not stated未披露Brochure states no capacity or rating conditions.样本未写容量和额定工况。
EVAPCO
eco-Air EAW-DA Double Stack
family 806–2,474系列 806–2,474
“2,750 MBH to 8,440 MBH”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露belt-drive NEMA motors皮带传动 NEMA 电机not stated未披露not stated未披露wetted adiabatic pads绝热湿帘double stack双层叠放Nominal range without conditions.名义范围,未写工况。
Güntner
High Density with hydroBLU
family 733–3,165系列 733–3,165
“2,500 – 10,800 MBH”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露4–22 fans, 36 in4–22 台风机,36 英寸not stated未披露3,581–13,233 × 3,581 (11′9″–43′5″ × 11′9″)3,581–13,233 × 3,581(11′9″–43′5″ × 11′9″)hydroBLU pads above a threshold超过阈值启用 hydroBLU 湿帘not stated未披露Nominal range without conditions; pads inactive below a set threshold; 'up to 70% less water than cooling towers'.名义范围,未写工况;低于设定阈值时湿帘不工作;“比冷却塔最多少用 70% 的水”。
LU-VE
Alfa V Mega VXX3 WETWALL
family 200–2,000系列 200–2,000
“200 to 2,000 kW (EN1048 standard)”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露WETWALL wetted panels; recirculation availableWETWALL 湿帘板;可选循环用水V-shapeV 型Same EN 1048 range as the dry version; no separate adiabatic capacity.与干式版本相同的 EN 1048 范围;没有单独的绝热容量。
Modine
ECO dry coolers, adiabatic configurations
not stated未披露not stated未披露not stated未披露not stated未披露primarily EC axial fans主要为 EC 轴流风机not stated未披露not stated未披露adiabatic pads or spray绝热湿帘或喷淋not stated未披露Marketing brochure; no capacities or ratings.宣传样本,没有容量和额定值。
Munters
DMI with INTELLIBATIC
family 50–1,500系列 50–1,500
“from 50 to 1500 kW”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露1–22 fans, 800 / 910 mm1–22 台风机,800 / 910 mmnot stated未披露not stated未披露INTELLIBATIC adiabatic systemINTELLIBATIC 绝热系统not stated未披露Family range only.只有系列容量范围。
Shenling
Data-center evaporative dry cooler (数据中心蒸发冷却干冷器)
family 500–2,000系列 500–2,000
“冷量覆盖500~2000kW”
no rating conditions未写工况
not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露not stated未披露evaporative assistance蒸发冷却辅助not stated未披露Family range only; dry and evaporative capacities not separated.只有系列容量范围;未区分干式与蒸发冷却容量。