Carrier AquaEdge 19MV4
Mag WCC; rated family 2,100–3,300 kW at 20 / 30 °C water and 49 °C condenser water.Mag WCC;额定 系列 2,100–3,300 kW,水温 20 / 30 °C,冷却水 49 °C。
20/30 °C chilled water, 49/55 °C condenser loop冷冻水 20/30 °C,冷凝回路 49/55 °C
Products · Chillers产品 · 冷水机组
How warm can chiller water run, and what is the chiller's job in a warm-water AI plant?冷水机组的供水能有多暖?在温水 AI 冷站里,冷机承担什么角色?
Data as of 2026-11-08, reviewed monthly.数据截至 2026-11-08,每月复核。Condition: sites designed for the warm-water point from the start前提:站点从一开始按温水工况设计
Chilled water冷冻水Hot refrigerant gas高温制冷剂气体A generic unit, not to scale.通用机组,不按比例。
Rows are grouped by chiller type (Mag WCC, oil-base WCC, ACC, ACS), warmest first. Solid dot: supply temperature at the vendor's rating point. Ring: highest supply temperature the vendor states. DC: the maker presents the line for data centers. Where a maker prints a pair such as "30-20 °C" without labels, the lower number is read as the supply. Hover a mark for its rating conditions and notes. Lines with neither value, and lines of other types, are left out. The 41 °C line is NVIDIA's reference example for facility water to CDUs (engineering context, not a chiller rating).按机组类型分组(Mag WCC、oil-base WCC、ACC、ACS),组内温度高者在前。实心点:厂商额定点的供水温度。空心圈:厂商标称的最高供水温度。DC:厂商面向数据中心推出的产品线。厂商只写“30-20 °C”这类数对而未注明时,较低的数值按供水读。悬停可看额定工况和说明。两者都没有的系列和其他类型的机组不画。41 °C 线是 NVIDIA 给 CDU 的设施水参考示例(工程背景,不是冷水机组额定值)。
Chilled-water supply at the rating point of the 10 lines rated at 18 °C or warmer (Carrier AquaEdge 19MV4; Vertiv Liebert OFC (water-cooled); Schneider Uniflair BCWC; Vertiv Liebert OFC (air-cooled); Schneider Uniflair XCA; Schneider Uniflair BCEC/BCEF; Smardt AeroPure AF; Airedale TurboChill DCS; Vertiv Liebert AFC (NA); Schneider Uniflair XRAC/XRAF); the classic comfort rating is 7 °C额定供水 18 °C 及以上的 10 个系列,其额定工况下的冷冻水供水温度(Carrier AquaEdge 19MV4;Vertiv Liebert OFC (water-cooled);Schneider Uniflair BCWC;Vertiv Liebert OFC (air-cooled);Schneider Uniflair XCA;Schneider Uniflair BCEC/BCEF;Smardt AeroPure AF;Airedale TurboChill DCS;Vertiv Liebert AFC (NA);Schneider Uniflair XRAC/XRAF);传统舒适性额定为 7 °C
Same unit, two rating points: 753 kW at 18/12 °C water, 35 °C outdoor air; 1,000 kW at 26/20 °C water, 33 °C outdoor air同一台机组的两个额定点:18/12 °C 水温,35 °C 室外 时 753 kW;26/20 °C 水温,33 °C 室外 时 1,000 kW
Highest stated maximum supply among the 55 matrix lines (Smardt Core); NVIDIA's example uses 41 °C facility water矩阵 55 个系列中标称的最高供水上限(Smardt Core);NVIDIA 示例的设施水为 41 °C
Over the next three years the chiller in an AI data center works alongside the dry cooler rather than giving way to it: GPUs that accept 45 °C water need about 41 °C facility water, which a dry cooler alone cannot make on hot hours.
That is an opportunity, because warmer water raises capacity.
The biggest challenge is speed: of the 55 lines here only Smardt's Core Series states 40 °C supply, without a rating table, the rest stop at 35 °C or below, and no line is rated above 24 °C supply, so makers must bring higher-temperature chillers to market quickly, while refrigerant rules (EU 2027, US EPA 2025–2027) force new low-GWP designs.
未来三年,AI 数据中心里的冷水机组会与干冷器互补,而不是被它取代:能接受 45 °C 水的 GPU 需要约 41 °C 的设施水,高温时段干冷器单独做不到。
这是机会,因为水温越高容量越大。
最大的挑战是速度:本页 55 个系列中只有 Smardt Core 系列标称 40 °C 供水,且没有公布额定表,其余系列最高 35 °C,额定供水都不超过 24 °C;厂商必须尽快推出能供更高温水的冷机,同时还要按制冷剂法规(欧盟 2027 年、美国 EPA 2025–2027 年)改用低 GWP 设计。
In a warm-water AI data center the chiller makes the facility water on the hours and for the loads the dry cooler cannot cover.在温水 AI 数据中心里,冷水机组承担干冷器覆盖不了的时段和负荷,为它们制备设施水。
DC chiller: the maker presents the line for data centersDC chiller:厂商面向数据中心推出的产品线 Other line of the type同类型的其他产品线 Stated plan, placed at the start of its window已公布的计划,放在其时间窗口的起点
Bands follow the chiller type the maker states (condenser and compressor). Lines of other types (water-cooled screw, scroll, absorption) are not drawn. Left column: current lines from the chiller matrix that launched before 2023 Q4 or whose launch date is not in the evidence base.分区按厂商写明的机组类型(冷凝方式和压缩机)。其他类型(水冷螺杆、涡旋、吸收式)不画。左列:冷机矩阵中 2023 年第四季度以前发布、或证据底座中没有发布日期的在售产品线。
| 18/12 °C water, 35 °C outdoor air18/12 °C 水温,35 °C 室外 | 753 kW | EER 3.91 |
|---|---|---|
| 26/20 °C water, 33 °C outdoor air26/20 °C 水温,33 °C 室外 | 1,000 kW | EER 4.64 |
STULZ CyberCool 2 ESO 7402 AHF, two rating points printed in the same brochure. Outdoor air also differs (35 vs 33 °C), so not all of the gain is from water temperature.STULZ CyberCool 2 ESO 7402 AHF,同一份样本中给出的两个额定点。室外温度也不同(35 °C 与 33 °C),所以增量并不全部来自水温。 Source来源
Schneider: first Uniflair XCA units begin shipping worldwide施耐德:首批 Uniflair XCA 机组开始全球发货
Planned计划, announced 2026-06,2026-06 公布 source来源
Johnson Controls plans to begin YORK YDAM shipments江森自控计划开始发运约克 YDAM
Planned计划, announced 2026-02-03,2026-02-03 公布 source来源
EU: stationary chillers above 12 kW containing F-gases with GWP of 750 or more may no longer be placed on the market, unless required to meet safety requirements欧盟:含 GWP 750 及以上含氟气体的 12 kW 以上固定式冷水机组不得再投放市场,满足安全要求所必需的除外
Planned计划, announced 2024-02,2024-02 公布 source来源
US EPA: data-center and IT cooling subsector GWP limit (below 700) begins美国 EPA:数据中心与 IT 冷却细分领域 GWP 上限(低于 700)生效
Planned计划, announced 2023-10,2023-10 公布 source来源
Each stays a plan until a source confirms it happened. Passing the window does not prove shipment.在有来源确认发生之前,各项都只是计划。时间窗口过去并不代表已经出货。
○ = not stated by the vendor. Values keep the vendor's own conditions; they are not a ranking. Choose "—" in the third box to compare two.○ = 厂商未标称。数值保留厂商自己的工况,不构成排名。第三个框选"—"即可只比较两款。
Rule: every matrix line whose rating point supplies 18 °C or warmer chilled water.规则:矩阵中额定工况供水 18 °C 及以上的全部系列。
Mag WCC; rated family 2,100–3,300 kW at 20 / 30 °C water and 49 °C condenser water.Mag WCC;额定 系列 2,100–3,300 kW,水温 20 / 30 °C,冷却水 49 °C。
20/30 °C chilled water, 49/55 °C condenser loop冷冻水 20/30 °C,冷凝回路 49/55 °C
Mag WCC; rated 2,400 kW at 20 / 26 °C water and 35 °C condenser water.Mag WCC;额定 2,400 kW,水温 20 / 26 °C,冷却水 35 °C。
EN 14511-2018; 400 V / 50 HzEN 14511-2018;400 V / 50 Hz
Mag WCC; rated 2,076.2 kW at 20 / 30 °C water.Mag WCC;额定 2,076.2 kW,水温 20 / 30 °C。
evaporator 30–20 °C, glycol 0%; condensing water leaving 35 °C; 400 V / 3 / 50 Hz蒸发器 30–20 °C,乙二醇 0%;冷却水出水 35 °C;400 V / 3 相 / 50 Hz
ACC; rated 1,800 kW at 20 / 26 °C water and 35 °C air.ACC;额定 1,800 kW,水温 20 / 26 °C,室外 35 °C。
EN 14511-2018; 400 V / 50 Hz; waterEN 14511-2018;400 V / 50 Hz;水
ACC; rated 2,540 kW at 20 / 30 °C water and 35 °C air.ACC;额定 2,540 kW,水温 20 / 30 °C,室外 35 °C。
water 30–20 °C, ambient 35 °C; glycol 0% or 20% (pairing unclear); 400 V / 3 / 50 Hz水 30–20 °C,室外 35 °C;乙二醇 0% 或 20%(对应关系不清);400 V / 3 相 / 50 Hz
ACC; rated 1,421.6 kW at 20 / 30 °C water and 35 °C air.ACC;额定 1,421.6 kW,水温 20 / 30 °C,室外 35 °C。
water 30–20 °C, glycol 0%, ambient 35 °C; 400 V / 3 / 50 Hz水 30–20 °C,乙二醇 0%,室外 35 °C;400 V / 3 相 / 50 Hz
ACC; rated 2,500 kW at 24 / 31 °C water and 45 °C air.ACC;额定 2,500 kW,水温 24 / 31 °C,室外 45 °C。
data-center model mix: 31 °C EWT, 24 °C LWT, 45 °C outdoor air数据中心型号组合:进水 31 °C,出水 24 °C,室外 45 °C
ACC; rated 1,850 kW at 20 / 30 °C water and 35 °C air.ACC;额定 1,850 kW,水温 20 / 30 °C,室外 35 °C。
50 Hz; 100% water (the 60 Hz table uses 115 °F ambient)50 Hz;100% 水(60 Hz 表的环境温度为 115°F)
ACS; rated 1,958 kW at 18.9 / 27.8 °C water and 35 °C air.ACS;额定 1,958 kW,水温 18.9 / 27.8 °C,室外 35 °C。
460 V / 60 Hz; ethylene glycol 30%460 V / 60 Hz;乙二醇 30%
ACS; rated 2,328.2 kW at 20 / 30 °C water and 35 °C air.ACS;额定 2,328.2 kW,水温 20 / 30 °C,室外 35 °C。
water 30–20 °C, glycol 0%, ambient 35 °C水 30–20 °C,乙二醇 0%,室外 35 °C
A date marks an event that happened; the plans are shown above with their windows. The full six-year roadmap is in the next rows.有日期的是已发生的事件;计划及其时间窗口见上文。完整六年路线图在下面。
All of them are in the full roadmap.全部见完整路线图。
Dated events from official sources. Planned events show the window the source states; passing the window does not prove shipment. No future model is inferred.来自官方来源的有日期事件。计划事件显示来源给出的时间窗口;窗口过去并不代表已经出货。不推测未来型号。
Listed companies behind the products on this page: 本页产品背后的上市公司:CarrierCarrier, DaikinDaikin, Johnson ControlsJohnson Controls, ModineModine, Schneider ElectricSchneider Electric, Shenling申菱环境, Trane TechnologiesTrane Technologies, VertivVertiv. Other makers: 其他厂商:STULZ (private非上市); Mitsubishi Electric (Climaveneta) (listed in Tokyo; not in this registry东京上市;不在本名单中); Smardt (not in this registry不在本名单中); DB (Dunham-Bush) (not in this registry不在本名单中). See the value-chain map查看产业链地图 · CDU deep diveCDU 深度分析
Specifications come from each vendor’s datasheet, engineering guide, brochure, product page or launch release, extracted twice by independent models and ruled against the source column by column. Events come from vendor, regulator and standards pages; each was checked by script on the page and by an independent model. Evidence cut-off 2026-11-08. Personal research, not investment advice.规格来自各厂商的数据表、工程手册、样本、产品页或发布稿,由两个独立模型分别提取,并逐列对照原文裁定。事件来自厂商、监管机构和标准组织的页面,每条都经脚本在原页面核对并由独立模型复核。证据截止 2026-11-08。个人研究,不构成投资建议。
Vendors state 304 of 636 displayed cells (a family range counts as a stated capacity). A value appears only in the column whose rating conditions it matches; capacities at different conditions are not ranked. Rows are sorted by capacity for reading only. Temperatures are converted to °C and tons to kW (1 ton = 3.517 kW) where the vendor printed other units. ○ = not stated by the vendor (explained once here, not repeated in words in each cell).表中 636 个单元格里,厂商披露了 304 个(系列容量范围算作已披露)。数值只放在工况相符的列;不同工况下的容量不做排名。行按容量排序,仅为方便阅读。厂商使用其他单位时,温度换算为 °C,冷吨换算为 kW(1 冷吨 = 3.517 kW)。○ = 厂商未标称(只在此说明一次,不在每格重复文字)。
| Company and line公司与产品 | Rated kW额定 kW | Chilled water supply / return °C冷冻水供 / 回水 °C | Condenser water in °C冷却水进水 °C | Efficiency at rating额定能效 | Input kW输入功率 kW | Part load部分负荷 | Max supply water °C最高供水 °C | Free cooling (vendor wording)自然冷却(厂商原文) | Refrigerant制冷剂 | Compressor压缩机 | Footprint L × W mm占地 长 × 宽 mm | Notes说明 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Smardt Ultra Series water-cooled [1] [2] | family 1,055–12,660系列 1,055–12,660 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 22 | not stated未披露 | R134a, R513A, R515B, R1234ze (R1234ze not for North America)R134a、R513A、R515B、R1234ze(北美不供 R1234ze) | oil-free magnetic-bearing centrifugal (Turbocor VTX 1600)无油磁悬浮离心(Turbocor VTX 1600) | not stated未披露 | Leaving chilled water "up to 22°C (71.6°F)"; the page adds that high-temperature capability depends on application and operating conditions. No rating table.冷冻水出水"最高 22°C(71.6°F)";页面注明高水温能力取决于应用和运行条件。没有额定表。 |
| Daikin Magnitude WME-C (Daikin Applied) [1] [2] | family 900–10,500系列 900–10,500 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 22.2 | not stated未披露 | R-513A or R-515BR-513A 或 R-515B | oil-free magnetic-bearing centrifugal (single, dual and quad compressors)无油磁悬浮离心(单、双、四压缩机) | not stated未披露 | Catalog CAT 641: 250–3,000 tons (900–10,500 kW as printed); evaporator leaving water up to 72 °F (22.2 °C, converted). The October 2025 release presents the WME-C Quad (2,000–3,000 tons) for data centers. No rating table.样本 CAT 641:250–3,000 冷吨(原文 900–10,500 kW);蒸发器出水最高 72°F(换算 22.2 °C)。2025 年 10 月发布稿把 WME-C Quad(2,000–3,000 冷吨)作为数据中心产品推出。没有额定表。 |
| Daikin Magnitude WME-E (Daikin Applied) [1] [2] [3] | family 1,230–8,615系列 1,230–8,615 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 29.4 | not stated未披露 | R-515BR-515B | oil-free magnetic-bearing centrifugal无油磁悬浮离心 | not stated未披露 | Engineering submittal ED 19164: ratings per project selection. Maximum leaving water 85 °F (29.4 °C) for single and dual configurations; quad configurations are limited to 80 °F (26.6 °C as printed); Daikin says limits depend on unit configuration. Range 350–2,450 tons (1,230–8,615 kW as printed in the catalog).工程提交资料 ED 19164:额定值按项目选型提供。单机头和双机头最高出水 85°F(29.4 °C);四机头限 80°F(原文 26.6 °C);大金说明限值取决于机组配置。样本范围 350–2,450 冷吨(原文 1,230–8,615 kW)。 |
| Vertiv CoolLoop Chiller water-cooled (China) [1] [2] | 6,000 WM4600SGH000Z GB/T 18430.1-2024 data-center conditionsGB/T 18430.1-2024 数据中心专用型工况 | 15 / null | 30 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | R134aR134a | oil-free magnetic-bearing centrifugal无油磁悬浮离心 | 6,800 × 3,060 | Rated at leaving chilled water 15 °C and condenser water in 30 °C (return water not printed). The table power row is the maximum operating power (1,030.4 kW), not input at rating, so no input is shown. The English APAC brochure gives 550–6,000 kW.额定工况:冷冻水出水 15 °C、冷却水进水 30 °C(未写回水)。表中功率是机组最大运行功率(1,030.4 kW),不是额定输入,因此不列输入功率。英文亚太样本为 550–6,000 kW。 |
| Johnson Controls YORK YZ (magnetic-bearing centrifugal) | family 530–5,627系列 530–5,627 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 26.7 | not stated未披露 | R-1233zdR-1233zd | magnetic-bearing centrifugal磁悬浮离心 | not stated未披露 | Engineering guide 161.01-EG1 (526): ratings by selection software only; leaving chilled water 36–80 °F (2.2–26.7 °C as printed).工程手册 161.01-EG1 (526):额定值只能通过选型软件获得;冷冻水出水 36–80°F(原文 2.2–26.7 °C)。 |
| Smardt Core Series water-cooled [1] [2] | family 160–5,625系列 160–5,625 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 40 | not stated未披露 | R134a, R513A, R515B, R1234ze (R1234ze not for North America)R134a、R513A、R515B、R1234ze(北美不供 R1234ze) | oil-free magnetic-bearing centrifugal; standard and high-lift无油磁悬浮离心;标准和高提升 | not stated未披露 | Leaving chilled water up to 40 °C (105 °F); no rating table. The brochure calls the high-temperature design "ideal for data center cooling", a suitability statement, so the line is not tagged DC. The 40 °C (105 °F) leaving-water limit is stated for the series; the maker does not say which compressor option (standard or high-lift) it needs.冷冻水出水最高 40 °C(105°F);没有额定表。样本称高水温设计"适合数据中心冷却",属于适用性说法,因此不标 DC。40 °C(105 °F)出水上限按系列给出;厂商未说明需要哪种压缩机选项(标准或高扬程)。 |
| Dunham-Bush WCM Prometheus | family 528–4,747系列 528–4,747 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | magnetic-bearing centrifugal, inverter-driven dual-stage磁悬浮离心,变频双级 | not stated未披露 | Product page lists ranges and features only; "Green Refrigerants" names no refrigerant. Modular WCM-M: 150–400 RT (528–1,406 kW).产品页只列范围和特点;"环保冷媒"未写明制冷剂。模块化 WCM-M:150–400 冷吨(528–1,406 kW)。 |
| Mitsubishi Electric TX-W-G05 [1] [2] | 4,092 TX-W-G05 6D00 (R513A) EN 14511; 400 V / 3 / 50 Hz; R513AEN 14511;400 V / 3 相 / 50 Hz;R513A | 7 / 12 | 30 | EN 14511 EER 6.11 kW/kWEN 14511 EER 6.11 kW/kW | not stated未披露 | ESEER 8.27 kW/kWESEER 8.27 kW/kW | not stated未披露 | not stated未披露 | R513A (R134a version also tabulated)R513A(另列 R134a 版本) | oil-free magnetic-bearing centrifugal, up to 6 compressors无油磁悬浮离心,最多 6 台压缩机 | 6,610 × 2,400 | Comfort rating: plant water 12/7 °C, source water 30/35 °C. The gross-value row gives 3,592–4,490 kW for the same size (EER 6.52); the R134a 6D00 is 4,147 kW (EN 14511). No leaving-water maximum stated.舒适性工况:用户侧 12/7 °C,热源侧 30/35 °C。同一型号的毛值为 3,592–4,490 kW(EER 6.52);R134a 版 6D00 为 4,147 kW(EN 14511)。未写最高出水温度。 |
| Johnson Controls YORK YMC2 Mod C | family 2,460–3,520系列 2,460–3,520 50 Hz50 Hz | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 21.1 | not stated未披露 | R-134a or R-513AR-134a 或 R-513A | single-stage magnetic-bearing centrifugal, oil-free单级磁悬浮离心,无油 | not stated未披露 | Engineering guide 160.89-EG1 (324), 50 Hz range; leaving chilled water selectable up to 70 °F (21.1 °C as printed). No rating table.工程手册 160.89-EG1 (324),50 Hz 系列;冷冻水出水可选至 70°F(原文 21.1 °C)。没有额定表。 |
| Carrier AquaEdge 19MV4 [1] [2] | family 2,100–3,300系列 2,100–3,300 20/30 °C chilled water, 49/55 °C condenser loop冷冻水 20/30 °C,冷凝回路 49/55 °C | 20 / 30 | 49 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | R-1234ze or R-515BR-1234ze 或 R-515B | two-stage magnetic-bearing centrifugal两级磁悬浮离心 | not stated未披露 | Capacity range is stated at 20/30 °C chilled water and a 49/55 °C condensation loop (the release adds "under AHRI conditions"); 20 °C is read as supply. COP 6.75 and IPLV 11.4 are at AHRI conditions, not at this point. "Chilled-water temperatures up to 35°C" does not say supply or return, so no maximum is shown.容量范围对应 20/30 °C 冷冻水和 49/55 °C 冷凝回路(发布稿另注"AHRI 工况");20 °C 按供水读取。COP 6.75 和 IPLV 11.4 是 AHRI 工况,不是此额定点。"冷冻水温度最高 35°C"没有说明是供水还是回水,因此不列最高供水。 |
| Modine / Airedale TurboChill Hydro | 2,250–3,000 TCW25RCUEU-N-L-0 nominal: 12/7 °C return/supply, 30/35 °C condenser water名义工况:回/供水 12/7 °C,冷却水 30/35 °C | 7 / 12 | 30 | up to EER 5.74最高 EER 5.74 | not stated未披露 | up to ESEER 8.51最高 ESEER 8.51 | 20 | not stated未披露 | R134a or R513AR134a 或 R513A | oil-free magnetic-bearing centrifugal无油磁悬浮离心 | 5,500 × 2,192 | Comfort-cooling rating (12/7 °C, condenser 30/35 °C); the brochure's best ESEER (8.98) is a different model.舒适性空调工况(12/7 °C,冷却水 30/35 °C);样本中最高 ESEER(8.98)属于另一型号。 |
| Carrier AquaEdge 19MV [1] [2] [3] | family 527–2,461系列 527–2,461 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | R-513A, R-515B or R-1234ze(E)R-513A、R-515B 或 R-1234ze(E) | two-stage magnetic-bearing centrifugal两级磁悬浮离心 | not stated未披露 | North American 19MV, 150–700 tons (527–2,461 kW as printed). Product data also lists a roller-element-bearing option on the 19MV3 frame; this record is the magnetic-bearing version. "As low as 0.52 kW/ton" full load has no rating conditions. No leaving-water range found in the sources read.北美 19MV,150–700 冷吨(原文 527–2,461 kW)。产品资料另列 19MV3 机架可选滚动轴承;本记录为磁悬浮版本。满负荷"低至 0.52 kW/冷吨"没有工况。所读资料中未找到出水温度范围。 |
| Vertiv Liebert OFC water-cooled (R134a) | 2,400 WT4200B EN 14511-2018; 400 V / 50 HzEN 14511-2018;400 V / 50 Hz | 20 / 26 | 35 | EER 7.7EER 7.7 | 312 | not stated未披露 | not stated未披露 | not stated未披露 | R134a (R1234ze table: WTZ210Z 2,000 kW, EER 8.83)R134a(R1234ze 系列:WTZ210Z 2,000 kW,EER 8.83) | oil-free magnetic-levitation centrifugal无油磁悬浮离心 | 6,000 × 1,600 | EMEA brochure: rated at evaporator 26→20 °C and condenser 35→40 °C; values marked preliminary. The en-us product page now says it is not available for the region; the brochure still serves.EMEA 样本:额定工况为蒸发器 26→20 °C、冷凝器 35→40 °C;数值标注为初步。en-us 产品页现显示该地区不可用;样本仍可下载。 |
| Schneider Electric Uniflair BCWC [1] [2] [3] | 2,076.2 BCWC 1604A (R1234ze) evaporator 30–20 °C, glycol 0%; condensing water leaving 35 °C; 400 V / 3 / 50 Hz蒸发器 30–20 °C,乙二醇 0%;冷却水出水 35 °C;400 V / 3 相 / 50 Hz | 20 / 30 | not stated未披露 | EER 9.11 kW/kWEER 9.11 kW/kW | 228 | SEPR HT 10.8SEPR HT 10.8 | 25 | not stated未披露 | R134a / R513A / R1234zeR134a / R513A / R1234ze | 1 to 4 oil-free centrifugal compressors (Turbocor)1–4 台无油离心压缩机(Turbocor) | 2,330 × 4,955 | Brochure (Nov 2025), R1234ze table. Bearing type is taken from the compressor name: the catalog lists BCWC as Turbocor, a magnetic-bearing compressor; the brochure says only "oil-free centrifugal". Entering condenser water is printed as "*-35°C". Chilled water "up to 25 °C" raises capacity up to 2.4 MW. Footprint as printed (length 2,330 × width 4,955 mm).样本(2025 年 11 月),R1234ze 表。轴承类型取自压缩机名称:样册把 BCWC 列为 Turbocor(磁悬浮压缩机);样本只写"无油离心"。冷却水进水原文印为"*-35°C"。冷冻水"最高 25 °C"时容量最高 2.4 MW。占地按原文(长 2,330 × 宽 4,955 mm)。 |
| Mitsubishi Electric TX2-W-G04-Z [1] [2] | family 284–2,071系列 284–2,071 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | R1234zeR1234ze | oil-free centrifugal, magnetic bearings无油离心,磁悬浮轴承 | not stated未披露 | IT-cooling (-Z) version on the MEHITS site, 284–2,071 kW (printed "284 - 2.071 kW"). The comfort TX2-W-G04 brochure rates at 12/7 °C and 30/35 °C (191–2,069 kW); that rating is not assigned to the -Z version. No leaving-water maximum stated.MEHITS 网站的 IT 冷却(-Z)版本,284–2,071 kW(原文"284 - 2.071 kW")。舒适性 TX2-W-G04 样本的额定工况为 12/7 °C、30/35 °C(191–2,069 kW),不套用到 -Z 版本。未写最高出水温度。 |
| STULZ CyberCool WaterTec | family 350–1,510系列 350–1,510 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 19 | optional可选 | R1234zeR1234ze | oil-free magnetic-bearing无油磁悬浮 | not stated未披露 | Product page: chilled water outlet 1–19 °C; no rating table.产品页:冷冻水出水 1–19 °C;没有额定表。 |
| Trane HSWE | 600 to over 1,500 RT for data centers (2110 to over 5276 kW, converted); 500–1,250 RT standard数据中心 600 至 1,500 冷吨以上(换算约 2110 至 5276 kW 以上);标准应用 500–1,250 冷吨 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 35 | not stated未披露 | not stated未披露 | magnetic-bearing centrifugal磁悬浮离心 | not stated未披露 | Asia Pacific launch release (July 2026); no product page found. Leaving chilled water "up to 35°C". "Up to" COP 7.3 (China GB standard) and IPLV 12.3 (AHRI) have no rating point, so they are not shown as ratings. Refrigerant not named ("readiness for next-generation HFO").亚太发布稿(2026 年 7 月);未找到产品页。冷冻水出水"最高 35°C"。COP 最高 7.3(中国国标)和 IPLV 最高 12.3(AHRI)没有额定点,不作为额定值。未写明制冷剂("可适配新一代 HFO")。 |
| Company and line公司与产品 | Rated kW额定 kW | Chilled water supply / return °C冷冻水供 / 回水 °C | Condenser water in °C冷却水进水 °C | Efficiency at rating额定能效 | Input kW输入功率 kW | Part load部分负荷 | Max supply water °C最高供水 °C | Free cooling (vendor wording)自然冷却(厂商原文) | Refrigerant制冷剂 | Compressor压缩机 | Footprint L × W mm占地 长 × 宽 mm | Notes说明 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Trane CenTraVac CDHH / CVHH [1] [2] | family 2,989–21,102系列 2,989–21,102 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 18.3 | integrated option (CVHH)集成选项(CVHH) | R-1233zdR-1233zd | multistage direct-drive semi-hermetic centrifugal; oil-pump lubrication多级直驱半封闭离心;油泵润滑 | not stated未披露 | Family 850–6,000+ tons, converted to kW (×3.517); "up to 21MW" on the page is the vendor IT-load figure. Chilled-water range 38–65 °F applies to the CDHH block; CVHH states only "down to 20°F". High lift up to 80 °F. The EMEA line card says up to 14 MW. The maximum is the top of the "Chilled-Water Range" the maker prints; the range is not labelled supply or return.系列 850–6,000+ 冷吨,按 ×3.517 换算为 kW;页面"最高 21MW"是厂商给出的 IT 负荷。冷冻水范围 38–65°F 属于 CDHH;CVHH 只写"低至 20°F"。高提升最高 80°F。EMEA 产品目录写最高 14 MW。最高值取自厂商列出的“冷冻水范围”上限;该范围未注明是供水还是回水。 |
| Carrier AquaEdge 19XR/19XRV [1] [2] | family 1,055–11,957系列 1,055–11,957 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | R-513A or R-515BR-513A 或 R-515B | semi-hermetic centrifugal, single- or two-stage; oil-lubricated journal bearings半封闭离心,单级或两级;油润滑滑动轴承 | not stated未披露 | Single-stage 300–550 tons (1,055–1,934 kW) and two-stage 600–3,400 tons (2,110–11,957 kW), as printed. No rating temperatures and no leaving-water range in the sources read.单级 300–550 冷吨(1,055–1,934 kW),两级 600–3,400 冷吨(2,110–11,957 kW),按原文。所读资料中没有额定温度和出水范围。 |
| Johnson Controls YORK YK Style H [1] [2] | family 879–10,500系列 879–10,500 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 30 | not stated未披露 | R-134a, R-513A, R-515B or R-1234zeR-134a、R-513A、R-515B 或 R-1234ze | single-stage open-drive centrifugal; forced oil lubrication单级开启式离心;强制油润滑 | not stated未披露 | Engineering guide 160.76-EG1 (1025): leaving chilled water selectable 36–86 °F (2.2–30 °C as printed). The larger YK Style J (900–3,600 tons) states the same 86 °F limit. Quick-start is an option, not a data-center line.工程手册 160.76-EG1 (1025):冷冻水出水可选 36–86°F(原文 2.2–30 °C)。更大的 YK Style J(900–3,600 冷吨)上限同为 86°F。快速启动是选项,不是数据中心产品线。 |
| Daikin McQuay WTCC | family 2,110–5,627系列 2,110–5,627 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | R134aR134a | two-stage centrifugal with built-in oil pump两级离心,内置油泵 | not stated未披露 | McQuay (Daikin group, China) product page. Full-load COP "up to 7.0" at Chinese national-standard conditions and IPLV up to 11.4 have no model or capacity, so they are not shown as ratings.麦克维尔(大金集团,中国)产品页。国标工况满负荷 COP"可达 7.0"和 IPLV 可达 11.4 没有对应型号或容量,不作为额定值。 |
| Johnson Controls YORK YK-HT [1] [2] | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | R-1234ze or R-515BR-1234ze 或 R-515B | two-stage economized centrifugal; integrated lubrication system两级经济器离心;集成润滑系统 | not stated未披露 | Preview (AHR Expo, February 2026); no capacity or rating table. Condenser leaving fluid up to 165 °F (73.9 °C) and lift up to 110 °F are hot-side values, not chilled water. It can make 44 °F chilled water and 140 °F hot water at the same time (an operating statement). Oil lubrication is read from "integrated lubrication system".预发布(2026 年 2 月 AHR 展);没有容量和额定表。冷凝器出水最高 165°F(73.9 °C)和提升最高 110°F 是热侧数值,不是冷冻水。可同时制取 44°F 冷冻水和 140°F 热水(运行说明)。油润滑依据"集成润滑系统"判断。 |
| Mitsubishi Electric CCS two-stage VSD centrifugal (China) | 1,758–3,000 kW (heading) or 1,758–3,517 kW (basic parameters)1,758–3,000 kW(标题)或 1,758–3,517 kW(基本参数) | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | R134aR134a | two-stage centrifugal; ball/roller bearings with oil pump两级离心;滚珠/滚柱轴承,油泵润滑 | not stated未披露 | Climaveneta China (克莱门特). The page prints two upper bounds (3,000 and 3,517 kW); both kept. No data-center wording for this line.克莱门特中国网站。页面给出两个上限(3,000 和 3,517 kW),均保留。本系列没有数据中心表述。 |
| Company and line公司与产品 | Rated kW额定 kW | Chilled water supply / return °C冷冻水供 / 回水 °C | Ambient at rating °C额定工况环境温度 °C | Efficiency at rating额定能效 | Input kW输入功率 kW | Part load部分负荷 | Max supply water °C最高供水 °C | Max ambient °C最高环境温度 °C | Free cooling (vendor wording)自然冷却(厂商原文) | Refrigerant制冷剂 | Compressor压缩机 | Footprint L × W mm占地 长 × 宽 mm | Notes说明 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Johnson Controls YORK YDAM [1] [2] [3] | family 2,500–3,350系列 2,500–3,350 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 28 | 55 | no free-cooling coils (maker: not necessary)无自然冷却盘管(厂商称不需要) | R-1234zeR-1234ze | magnetic-bearing centrifugal磁悬浮离心 | 16,154 × 2,591 | Family "710–950 TR (2,500–3,350 kW)" and "leaving-water setpoint flexibility from 60°F to 82.4°F (15.6°C to 28°C)" from the YDAM brochure (26-jciappequ-2085) listed on the York product page, saved manually on 2026-11-08 because the page blocks automated readers. The brochure prints "Up to 3.5 MW (3.3 MW nominal)"; the launch release says up to 3.5 MW (no conditions). Footprint, refrigerant and the −28.9 to 55 °C ambient range from engineering guide 160.98-EG1 (1126); footprint is the YDAM 3000 frame (636 × 102 in, converted). "45°C warm-water cooling" in the release is the GPU loop, not the chiller leaving water.系列“710–950 冷吨(2,500–3,350 kW)”和“出水设定 60°F 至 82.4°F(15.6 °C 至 28 °C)”取自约克产品页所列的 YDAM 样本(26-jciappequ-2085),因该页屏蔽自动读取,于 2026-11-08 手动保存。样本写“最高 3.5 MW(名义 3.3 MW)”;发布稿写最高 3.5 MW(未注明工况)。占地、制冷剂和 −28.9 至 55 °C 环境温度取自工程手册 160.98-EG1 (1126);占地为 YDAM 3000 机架(636 × 102 英寸,换算)。发布稿中的“45°C 温水冷却”指 GPU 回路,不是冷机出水温度。 |
| Trane Air-Cooled Magnetic Bearing Chiller TCA [1] [2] [3] | family 1,055–2,989系列 1,055–2,989 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 29.4 | 54.4 | optional compressor-assisted economizer; no separate free-cooling coils可选压缩机辅助经济器;无单独自然冷却盘管 | R-515B or R-1234zeR-515B 或 R-1234ze | oil-free magnetic-bearing centrifugal无油磁悬浮离心 | 17,069 × 3,048 | Family 300–850 tons, converted to kW; the PEP says 100–850 tons. Leaving water 60–85 °F in the May 2026 brochure (max converted 29.4 °C); the product page prints "Cooling: 60°F to 86°F" without saying leaving. Footprint is the TCAB850 frame (672 × 120 in, converted), "all values are estimated".系列 300–850 冷吨,换算为 kW;PEP 写 100–850 冷吨。2026 年 5 月样本出水 60–85°F(最高换算 29.4 °C);产品页印"制冷:60°F 至 86°F",未说明是出水。占地为 TCAB850 机架(672 × 120 英寸,换算),"所有数值为估计"。 |
| Schneider Electric Uniflair XCA (XCAC / XCAF free cooling) [1] [2] | 2,540 XCAC 2524A, with subcooling economizer (R1234ze) water 30–20 °C, ambient 35 °C; glycol 0% or 20% (pairing unclear); 400 V / 3 / 50 Hz水 30–20 °C,室外 35 °C;乙二醇 0% 或 20%(对应关系不清);400 V / 3 相 / 50 Hz | 20 / 30 | 35 | EER 4.66EER 4.66 | 544.5 | not stated未披露 | 33 | 52 | integrated (XCAF models)集成(XCAF 型号) | R1234zeR1234ze | oil-free magnetic-bearing centrifugal无油磁悬浮离心 | 13,473 × 2,311 | Brochure (June 2026), XCAC 2524A: 2,540 kW, EER 4.66 with the subcooling economizer; 2,390 kW, EER 4.46 without. Each page prints a glycol 0% and a glycol 20% footnote and the text does not tie them to a table. Outlet water up to 33 °C applies to the XCAF free-cooling models. The release gives 1,300–2,500 kW (also 1,200–2,500 kW).样本(2026 年 6 月),XCAC 2524A:带过冷经济器 2,540 kW、EER 4.66;不带 2,390 kW、EER 4.46。每页同时印有乙二醇 0% 和 20% 两个脚注,文本未说明各对应哪张表。出水最高 33 °C 适用于 XCAF 自然冷却型号。发布稿为 1,300–2,500 kW(另写 1,200–2,500 kW)。 |
| Smardt AeroPure AF Series [1] [2] [3] | 2,500 AF240.4G.F22.40.S4 (R1234ze/R515B) data-center model mix: 31 °C EWT, 24 °C LWT, 45 °C outdoor air数据中心型号组合:进水 31 °C,出水 24 °C,室外 45 °C | 24 / 31 | 45 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 54 | not stated未披露 | R134a, R513A, R515B or R1234zeR134a、R513A、R515B 或 R1234ze | oil-free magnetic-bearing centrifugal无油磁悬浮离心 | not stated未披露 | Brochure data-center model mix: nominal capacities at 24 °C LWT; R1234ze/R515B models at 31 °C EWT and 45 °C OAT (largest 2,500 kW), R513A/R134a models at 36 °C EWT and 52 °C OAT (largest 1,640 kW). Condition labels are paired with tables by text order. The launch release states EER up to 16 at 88 °F EWT, 74 °F LWT, 113 °F OAT, without capacity.样本数据中心型号组合:名义容量对应出水 24 °C;R1234ze/R515B 型号为进水 31 °C、室外 45 °C(最大 2,500 kW),R513A/R134a 型号为进水 36 °C、室外 52 °C(最大 1,640 kW)。工况标签按文本顺序对应表格。发布稿写 EER 最高 16(进水 88°F、出水 74°F、室外 113°F),没有对应容量。 |
| Trane HSAG | family 703–2,110系列 703–2,110 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 30 | 52 | not stated未披露 | R1234zeR1234ze | oil-free magnetic-bearing centrifugal无油磁悬浮离心 | not stated未披露 | Asia Pacific launch release (February 2026): 200–600 tons "under data center conditions" (converted to kW; conditions not given), chilled water supply up to 30 °C, operation to 52 °C ambient in the High Ambient configuration. COP "exceeding 5.0" at typical data-center conditions is not shown as a rating.亚太发布稿(2026 年 2 月):"数据中心工况下"200–600 冷吨(换算为 kW;未给出工况),冷冻水供水最高 30 °C,高环温配置可在 52 °C 环境运行。典型数据中心工况下 COP"超过 5.0"不作为额定值。 |
| Daikin Pathfinder AWM (Daikin Applied) [1] [2] [3] | family 1,407–2,110系列 1,407–2,110 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 30 | 57.2 | optional integrated waterside economizer (IWSE)可选集成水侧经济器(IWSE) | R-515B or R-1234ze(E)R-515B 或 R-1234ze(E) | oil-free magnetic-bearing centrifugal无油磁悬浮离心 | not stated未披露 | Engineering submittal ED 19152 (July 2026): 400–600 tons (converted), no rating table; leaving chilled water 57–86 °F (13.9–30 °C) with water only. The product page prints both 400–600 and 400–550 tons and states a 135 °F maximum ambient (converted 57.2 °C); the submittal says maximum ambient depends on configuration.工程提交资料 ED 19152(2026 年 7 月):400–600 冷吨(换算),没有额定表;纯水时冷冻水出水 57–86°F(13.9–30 °C)。产品页同时印有 400–600 和 400–550 冷吨,并写最高环境温度 135°F(换算 57.2 °C);提交资料称最高环境温度取决于配置。 |
| Vertiv CoolLoop Chiller air-cooled (China) [1] [2] | 2,000 CM4200SGHC003 GB/T 18430.1-2024 data-center conditions; 380 V / 3 / 50 HzGB/T 18430.1-2024 数据中心专用型工况;380 V / 3 相 / 50 Hz | 15 / null | 35 | not stated未披露 | not stated未披露 | not stated未披露 | 25 | not stated未披露 | optional configuration可选配置 | R134aR134a | oil-free magnetic-bearing centrifugal无油磁悬浮离心 | 17,250 × 2,260 | Rated at leaving chilled water 15 °C and 35 °C dry bulb (return water printed as "-"). The power row is maximum operating power, not input at rating. Leaving water up to 25 °C. The English APAC brochure gives 350–2,200 kW.额定工况:冷冻水出水 15 °C、干球 35 °C(回水原文为"-")。功率行是最大运行功率,不是额定输入。出水最高 25 °C。英文亚太样本为 350–2,200 kW。 |
| Modine / Airedale TurboChill DCS | 1,850 TCC14R28K 50 Hz; 100% water (the 60 Hz table uses 115 °F ambient)50 Hz;100% 水(60 Hz 表的环境温度为 115°F) | 20 / 30 | 35 | EER 4EER 4 | not stated未披露 | not stated未披露 | 26 | 55 | optional (TCF models)可选(TCF 型号) | R1234zeR1234ze | oil-free centrifugal (Turbocor)无油离心(Turbocor) | 16,207 × 2,200 | Rated at 20/30 °C water and 35 °C ambient; supply water up to 26 °C.额定工况为 20/30 °C 水温、35 °C 环境温度;供水最高 26 °C。 |
| Mitsubishi Electric TX2-FC-G04-Z [1] [2] | family 840–1,800系列 840–1,800 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 26 | not stated未披露 | integrated (glycol and no-glycol versions)集成(乙二醇和无乙二醇版本) | R1234zeR1234ze | oil-free magnetic-levitation centrifugal无油磁悬浮离心 | not stated未披露 | MEHITS IT-cooling page: chilled water "up to 26 °C" with delta T up to 20 K; 840–1,800 kW (printed "840 - 1.800 kW"). No rating table in the readable sources (the NZ technical-data PDF is image-only).MEHITS IT 冷却页面:冷冻水"最高 26 °C",温差最高 20 K;840–1,800 kW(原文"840 - 1.800 kW")。可读资料中没有额定表(新西兰技术数据 PDF 为图片)。 |
| Vertiv Liebert OFC air-cooled (R134a) | 1,800 CT4135B EN 14511-2018; 400 V / 50 Hz; waterEN 14511-2018;400 V / 50 Hz;水 | 20 / 26 | 35 | EER 4.9EER 4.9 | 368 | not stated未披露 | not stated未披露 | not stated未披露 | freecooling versions (FT / FTZ)自然冷却版本(FT / FTZ) | R134a (R1234ze table: CTZ130Z 1,600 kW, EER 5.16)R134a(R1234ze 系列:CTZ130Z 1,600 kW,EER 5.16) | oil-free magnetic-levitation centrifugal无油磁悬浮离心 | 12,910 × 2,250 | EMEA brochure: rated at water 26→20 °C and 35 °C air; values marked preliminary. Freecooling FT4120B: 1,400 kW, EER 3.99 with 30% ethylene glycol.EMEA 样本:额定工况为水 26→20 °C、室外 35 °C;数值标注为初步。自然冷却型 FT4120B:1,400 kW,EER 3.99(30% 乙二醇)。 |
| Smardt AE Series air-cooled [1] [2] | family 140–1,786系列 140–1,786 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 30 | 52 | not stated未披露 | R134a, R513A, R515B or R1234zeR134a、R513A、R515B 或 R1234ze | oil-free magnetic-bearing centrifugal; standard and high-lift无油磁悬浮离心;标准和高提升 | not stated未披露 | Page header 140–1,760 kW, specification table 140–1,786 kW. The brochure offers high leaving chilled water "up to 30°C (For Data Center application)", an application option, so the line is not tagged DC. The AF Series is a development of the AE Series.页头 140–1,760 kW,规格表 140–1,786 kW。样本提供"最高 30°C 高出水(用于数据中心)",属于应用选项,因此不标 DC。AF 系列由 AE 系列发展而来。 |
| Mitsubishi Electric MECH-iC [1] [2] [3] [4] | 1,768 MECH-iC 500T gross; AHRI 550/590; 460 V / 3 / 60 Hz; 100% water毛值;AHRI 550/590;460 V / 3 相 / 60 Hz;100% 水 | 18.9 / 27.8 direction unclear (see note)方向不明(见说明) | 42 | COP 3.88 kW/kWCOP 3.88 kW/kW | 456 | not stated未披露 | 25 | 51.7 | not stated未披露 | R-515BR-515B | oil-free magnetic-bearing centrifugal无油磁悬浮离心 | 9,510 × 2,259 | Data sheet rating prints water as "66°F/82°F (18.9°C/27.8°C) entering/leaving", which cannot be the direction for a chiller, so no rated supply is shown. Optimised for 65–75 °F leaving water; maximum 77 °F (25.0 °C, converted): the brochure says it "covers supply temperatures ranging from ~59–77°F" and the MEHITS page says "up to 77°F". Family is the printed 350 and 500 tons (1.2 and 1.75 MW); MEHITS lists 1,349–1,948 kW. NPLV 0.46 kW/ton on the page is an illustrative example, not shown as a rating. Footprint 31.2 × 7.41 ft, converted.数据表额定工况原文为"66°F/82°F(18.9°C/27.8°C)进/出水",对冷水机组不可能成立,因此不列额定供水。针对 65–75°F 出水优化;最高 77°F(换算 25.0 °C):样本写供水覆盖约 59–77°F,MEHITS 页面写"最高 77°F"。系列按原文 350 和 500 冷吨(1.2 和 1.75 MW);MEHITS 列 1,349–1,948 kW。页面上 NPLV 0.46 kW/冷吨是示例,不作为额定值。占地 31.2 × 7.41 英尺,换算。 |
| Dunham-Bush ACM-AE Athena [1] [2] | family 306–1,765系列 306–1,765 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | R134a/R513AR134a/R513A | magnetic-bearing centrifugal, inverter-driven dual-stage磁悬浮离心,变频双级 | not stated未披露 | Product page 87–502 RT (306–1,765 kW as printed); the August 2023 launch post says 90–500 RT and "specially designed for Data Centre". No rating table.产品页 87–502 冷吨(原文 306–1,765 kW);2023 年 8 月发布帖写 90–500 冷吨,"专为数据中心设计"。没有额定表。 |
| Johnson Controls YORK YVAM [1] [2] [3] [4] [5] | family 880–1,750系列 880–1,750 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 32 | 55 | not stated未披露 | R-1234zeR-1234ze | magnetic-bearing centrifugal磁悬浮离心 | not stated未披露 | Family "250 ton to 500 ton (880 kW to 1750 kW), 60 Hz" from engineering guide 160.88-EG1 (526, May 2026); the 50 Hz leaflet covers "YVAM 1100 to 1800 kW" and lists "Leaving fluid temperatures up to 32°C" among its options and accessories (the 60 Hz guide prints no range); the sales brochure says it "can also produce 32°C chilled water for liquid-cooled servers". All three are listed on the York product page and were saved manually on 2026-11-08 because the page blocks automated readers. The European launch release (March 2025) gives chilled water +15 to 30 °C and ambient −29 to +55 °C. First launched 18 May 2023.系列“250 至 500 冷吨(880 至 1750 kW),60 Hz”取自工程手册 160.88-EG1(526,2026 年 5 月);50 Hz 单页覆盖“YVAM 1100 至 1800 kW”,在选项与附件中列出“出液温度最高 32 °C”(60 Hz 手册未给范围);销售样本写明“也可为液冷服务器提供 32 °C 冷冻水”。三份资料均列于约克产品页,因该页屏蔽自动读取,于 2026-11-08 手动保存。欧洲发布稿(2025 年 3 月)写冷冻水 +15 至 30 °C、环境 −29 至 +55 °C。首次发布于 2023 年 5 月 18 日。 |
| Schneider Electric Uniflair BCEC / BCEF [1] [2] | 1,421.6 BCEC 1103A (R1234ze) water 30–20 °C, glycol 0%, ambient 35 °C; 400 V / 3 / 50 Hz水 30–20 °C,乙二醇 0%,室外 35 °C;400 V / 3 相 / 50 Hz | 20 / 30 | 35 | EER 4.58EER 4.58 | 310.1 | SEPR HT 7.8SEPR HT 7.8 | not stated未披露 | not stated未披露 | free-cooling version (BCEF)自然冷却版本(BCEF) | R1234ze (R134a and R513A tables also printed)R1234ze(另列 R134a 和 R513A 表) | oil-free centrifugal (Turbocor)无油离心(Turbocor) | 12,025 × 2,201 | Brochure (October 2023), R1234ze table; the R134a table gives 1,807.8 kW (EER 4.31) for the same size. Bearing type is taken from the compressor name (Turbocor in the catalog); the brochure says only "oil-free centrifugal". The saved sources call it mission-critical, not a data-center line.样本(2023 年 10 月),R1234ze 表;R134a 表同型号为 1,807.8 kW(EER 4.31)。轴承类型取自压缩机名称(样册写 Turbocor);样本只写"无油离心"。所读资料称其用于关键任务,不是数据中心专用产品线。 |
| Mitsubishi Electric TECS2-G05 [1] [2] [3] | 1,170 TECS2-G05 /SL-CA 1154 EN 14511 net; 400 V / 3 / 50 Hz (Europe)EN 14511 净值;400 V / 3 相 / 50 Hz(欧洲) | 7 / 12 | 35 | undefined EER 3.11 kW/kWundefined EER 3.11 kW/kW | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | R513AR513A | centrifugal with magnetic bearings磁悬浮离心 | 11,500 × 2,260 | Comfort rating (EN 14511): plant water 12/7 °C, air 35 °C. The current brochure confirms the 1154 values of the 2019-02 data book (1,170 kW, EER 3.11) and the 11,500 × 2,260 mm frame; family 218–1,313 kW. No dated launch found.舒适性工况(EN 14511):用户侧 12/7 °C,室外 35 °C。现行样本与 2019-02 数据手册的 1154 数值一致(1,170 kW,EER 3.11),机架 11,500 × 2,260 mm;系列 218–1,313 kW。未找到有日期的发布。 |
| Carrier AquaEdge 30CF [1] [2] | more than 3,000 (conditions not stated)超过 3,000(未注明工况) | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 60 | not stated未披露 | HFO-1234ze(E); also R-515BHFO-1234ze(E);另有 R-515B | two-stage magnetic-bearing centrifugal两级磁悬浮离心 | not stated未披露 | Launch release (February 2026) and brochure; no rating table. Capacity is a lower bound without conditions ("more than 3 MW ... depending on ambient"). Operation from −20 to 140 °F (−28.8 to 60 °C) ambient.2026 年 2 月发布稿和样本;没有额定表。容量为下限,无工况("超过 3 MW,取决于环境温度")。环境温度 −20 至 140°F(−28.8 至 60 °C)可运行。 |
| Company and line公司与产品 | Rated kW额定 kW | Chilled water supply / return °C冷冻水供 / 回水 °C | Ambient at rating °C额定工况环境温度 °C | Efficiency at rating额定能效 | Input kW输入功率 kW | Part load部分负荷 | Max supply water °C最高供水 °C | Max ambient °C最高环境温度 °C | Free cooling (vendor wording)自然冷却(厂商原文) | Refrigerant制冷剂 | Compressor压缩机 | Footprint L × W mm占地 长 × 宽 mm | Notes说明 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Mitsubishi Electric i-FX2-G04-Z [1] [2] | family 563–2,443系列 563–2,443 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 25 | 52 | not stated未披露 | R1234zeR1234ze | semi-hermetic variable-speed screw半封闭变频螺杆 | not stated未披露 | MEHITS IT-cooling page: evaporator outlet 6–25 °C, 15 K maximum ΔT; full load to 52 °C outdoor air with dedicated accessories. The comfort i-FX2-G04 brochure gives 380–1,676 kW.MEHITS IT 冷却页面:蒸发器出水 6–25 °C,最大温差 15 K;配专用附件时室外 52 °C 满负荷运行。舒适性 i-FX2-G04 样本为 380–1,676 kW。 |
| Schneider Electric Uniflair XRAC / XRAF | 2,328.2 XRAC 7222H, stepless screw (R134a) water 30–20 °C, glycol 0%, ambient 35 °C水 30–20 °C,乙二醇 0%,室外 35 °C | 20 / 30 | 35 | EER 3.65EER 3.65 | 638.1 | not stated未披露 | 25 | 50 | free-cooling version (XRAF)自然冷却版本(XRAF) | R134a (R513A, R1234ze and R1234yf as alternatives)R134a(可选 R513A、R1234ze、R1234yf) | stepless screw; hybrid inverter and full inverter options无级调节螺杆;可选混合变频和全变频 | not stated未披露 | Brochure, stepless R134a table, largest size 7222H. The brochure also says "up to 1.5MW (nominal) and 2.2MW with 20/30°C"; the catalog prints 600–2,050 and 600–2,200 kW. Outlet water up to 25 °C for IT applications; ambient up to 50 °C.样本,无级 R134a 表,最大型号 7222H。样本另写"名义最高 1.5MW,20/30°C 时 2.2MW";样册印 600–2,050 和 600–2,200 kW。IT 应用出水最高 25 °C;环境温度最高 50 °C。 |
| Vertiv Liebert AFC inverter screw (EMEA, R1234ze) | family 650–2,200系列 650–2,200 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 56 | optimized free-cooling coils优化的自然冷却盘管 | R1234zeR1234ze | inverter screw变频螺杆 | not stated未披露 | EMEA product family page: 650–2,200 kW with R1234ze, a different spec family from the North American datasheet (CH3 screw, R513A). Listed nominal capacities reach 2,253 kW (CIZ220) without rating conditions. Ambient −25 to +56 °C.EMEA 产品系列页:650–2,200 kW,R1234ze,与北美数据表(CH3 螺杆,R513A)规格系列不同。所列名义容量最高 2,253 kW(CIZ220),未注明工况。环境温度 −25 至 +56 °C。 |
| Carrier AquaForce 30XF (Europe) [1] [2] | family 390–2,100系列 390–2,100 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 55 | built-in hydronic free cooling (FreeBoost); glycol-free option内置水侧自然冷却(FreeBoost);可选无乙二醇 | R-1234zeR-1234ze | variable-speed screw变频螺杆 | not stated未披露 | UK product page: 390–2,100 kW; the April 2024 launch release says 400–2,100 kW. "Maintains 26 °C leaving water temperature, even with 55 °C OAT" is an operating statement, not a rating or a stated maximum.英国产品页:390–2,100 kW;2024 年 4 月发布稿写 400–2,100 kW。"即使在 55 °C 室外温度下也能保持 26 °C 出水"是运行说明,不是额定值,也不是标称上限。 |
| Daikin Pathfinder AWV (Daikin Applied) [1] [2] [3] | family 350–1,985系列 350–1,985 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | integrated (closed-loop free cooling version)集成(闭式自然冷却版本) | R-513A or R-515BR-513A 或 R-515B | screw with variable volume ratio (VVR)可变容积比(VVR)螺杆 | not stated未披露 | Catalog CAT 640: 100–565 tons (350–1,985 kW as printed). The page claims "highest leaving chilled water capabilities" without a number. Daikin Applied lists AWV among its data-center chillers.样本 CAT 640:100–565 冷吨(原文 350–1,985 kW)。页面称"出水能力最高",但没有数值。大金应用把 AWV 列入数据中心冷水机组。 |
| Vertiv Liebert AFC (CH3 screw, R513A) | 1,958 CH3175 460 V / 60 Hz; ethylene glycol 30%460 V / 60 Hz;乙二醇 30% | 18.9 / 27.8 | 35 | EER 14.1 Btu/W-hEER 14.1 Btu/W-h | 474 | not stated未披露 | not stated未披露 | not stated未披露 | integrated (FH / FIZ versions)集成(FH / FIZ 型号) | R513A (R1234ze, R515B options)R513A(可选 R1234ze、R515B) | screw螺杆 | 13,386 × 2,362 | Vendor marks the table "Preliminary data"; rated at 82→66 °F fluid with 30% ethylene glycol and 95 °F ambient (°C values converted). Family headline 900–1,800 kW is below the largest tabulated model (1,958 kW); both kept as printed.厂商标注为初步数据;额定工况为 82→66°F 流体(30% 乙二醇)、95°F 环境温度(°C 为换算值)。系列标题 900–1,800 kW 低于表中最大型号 1,958 kW,两者均按原文保留。 |
| Trane Ascend ACR (data-center configuration) | family 528–1,934系列 528–1,934 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 22.2 | 55 | factory-integrated option工厂集成选项 | R-1234zeR-1234ze | variable-speed screw变频螺杆 | not stated未披露 | Family 150–550 nominal tons from the IOM title on the page, converted to kW; "Up to 2 MW" has no rating conditions. Chilled-water range 40–72 °F (max converted 22.2 °C); ambient up to 131 °F, with short excursions above. The maximum is the top of the "Chilled-Water Range" the maker prints; the range is not labelled supply or return.系列 150–550 名义冷吨取自页面上的 IOM 标题,换算为 kW;"最高 2 MW"未注明工况。冷冻水范围 40–72°F(最高换算 22.2 °C);环境温度最高 131°F,可短时超出。最高值取自厂商列出的“冷冻水范围”上限;该范围未注明是供水还是回水。 |
| Johnson Controls YORK YVAA Style B | family 525–1,934系列 525–1,934 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 23.9 | 55 | not stated未披露 | R-134a, R-513A or R-1234zeR-134a、R-513A 或 R-1234ze | variable-speed screw变频螺杆 | not stated未披露 | Engineering guide 201.47-EG1 (1225): above 72 °F (22.2 °C) leaving liquid "contact your nearest Johnson Controls Sales Office", so 22.2 °C is the edge of the standard range; the drawn maximum is the physical-data tables' 40/75 °F (4.4/23.9 °C), printed with that footnote. Ambient −10 to 131 °F (−23 to 55 °C).工程手册 201.47-EG1 (1225):出液高于 72°F(22.2 °C)需"联系江森自控销售",因此 22.2 °C 是标准范围的上沿;图中最高值取自物理参数表的 40/75°F(4.4/23.9 °C),带同一脚注。环境温度 −10 至 131°F(−23 至 55 °C)。 |
| STULZ CyberCool Explorer WS | family 280–1,860系列 280–1,860 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 25 | 48 | integrated集成 | R1234ze (WSA and WSI) or R513A (WSA)R1234ze(WSA 和 WSI)或 R513A(WSA) | screw, stepless (WSA) or inverter (WSI)螺杆,无级调节(WSA)或变频(WSI) | not stated未披露 | Product page: designed for data centers, water up to +32 °C inlet and +25 °C outlet. The only capacity with conditions is the WSJ563 annual operating-hours example (nominal 1,646 kW at 32/20 °C water and +35 °C ambient), not a rating table, so no rating is shown. Full load to +48 °C outside air for WSA. The technical tab gives 178–1,451 kW (WSA) and 215–1,265 kW (WSI), basis not stated.产品页:面向数据中心设计,水温进水最高 +32 °C、出水最高 +25 °C。唯一带工况的容量是 WSJ563 全年运行小时示例(水 32/20 °C、环境 +35 °C 时名义 1,646 kW),不是额定表,因此不列额定值。WSA 室外 +48 °C 满负荷运行。技术参数页为 178–1,451 kW(WSA)和 215–1,265 kW(WSI),未写工况。 |
| Carrier AquaForce 30XF (North America) | family 1,400–1,758系列 1,400–1,758 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 60 | integrated free-cooling coils集成自然冷却盘管 | R-513AR-513A | variable-speed screw变频螺杆 | not stated未披露 | US product page: 400–500 tons (1,400–1,758 kW as printed) with R-513A, a different spec family from the European 30XF (R-1234ze, up to 2,100 kW). Ambient −20 to 140 °F (max converted 60 °C).美国产品页:400–500 冷吨(原文 1,400–1,758 kW),R-513A,与欧洲 30XF(R-1234ze,最高 2,100 kW)规格系列不同。环境温度 −20 至 140°F(最高换算 60 °C)。 |
| Dunham-Bush ACHX-C Helios | family 317–1,545系列 317–1,545 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 52 | not stated未披露 | not stated未披露 | horizontal screw卧式螺杆 | not stated未披露 | Product page lists ranges and features only; "Green Refrigerants" names no refrigerant. The ACHX family also lists B, D and DVE versions.产品页只列范围和特点;"环保冷媒"未写明制冷剂。ACHX 系列另有 B、D 和 DVE 版本。 |
| Johnson Controls YORK YVFA | family 400–1,340系列 400–1,340 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | 21.1 | 55 | integrated free-cooling coils集成自然冷却盘管 | R-134a, R-513A or R-1234zeR-134a、R-513A 或 R-1234ze | variable-speed screw变频螺杆 | not stated未披露 | Engineering guide 201.31-EG1 (1026): "maximum leaving liquid temperature of 70°F (21.1°C)", which "may be higher" for CTS170 compressors or R-1234ze; a physical-data footnote asks to contact sales above 60 °F (15.6 °C). Ambient −20 to 131 °F (−28.9 to 55 °C).工程手册 201.31-EG1 (1026):"最高出液温度 70°F(21.1°C)",CTS170 压缩机或 R-1234ze 机型"可能更高";物理参数表脚注要求高于 60°F(15.6 °C)时联系销售。环境温度 −20 至 131°F(−28.9 至 55 °C)。 |
| Mitsubishi Electric MECH-iF (G04 / G05) [1] [2] [3] | family 339–921系列 339–921 EN 14511 net, conditions of the "up to" EEREN 14511 净值,"最高"EER 的工况 | 7 / 12 | 35 | up to (G04) EER 3.3最高(G04) EER 3.3 | not stated未披露 | not stated未披露 | 20 | 50 | not stated未披露 | R1234ze (G04) or R513A (G05)R1234ze(G04)或 R513A(G05) | variable-speed single screw变频单螺杆 | not stated未披露 | Brochure: 339–921 kW; "up to" EER 3.3 (G04) at evaporator 12/7 °C and 35 °C air, net, with no capacity attached. Leaving water up to +20 °C (down to −10 °C); ambient up to 50 °C (48 °C for G05). The MEHITS IT-cooling page lists MECH-iF-G04 at 471–1,007 kW and the UK launch says 345–921 kW.样本:339–921 kW;"最高" EER 3.3(G04),工况为蒸发器 12/7 °C、室外 35 °C,净值,无对应容量。出水最高 +20 °C(最低 −10 °C);环境温度最高 50 °C(G05 为 48 °C)。MEHITS IT 冷却页面列 MECH-iF-G04 为 471–1,007 kW,英国发布稿为 345–921 kW。 |
| Company and line公司与产品 | Rated kW额定 kW | Chilled water supply / return °C冷冻水供 / 回水 °C | Ambient at rating °C额定工况环境温度 °C | Efficiency at rating额定能效 | Input kW输入功率 kW | Part load部分负荷 | Max supply water °C最高供水 °C | Max ambient °C最高环境温度 °C | Free cooling (vendor wording)自然冷却(厂商原文) | Refrigerant制冷剂 | Compressor压缩机 | Footprint L × W mm占地 长 × 宽 mm | Notes说明 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Shenling Free-cooling air-cooled chiller (自然冷却风冷冷水机组) | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | integrated集成 | R134aR134a | not stated未披露 | not stated未披露 | Product page states no capacity or rating conditions and does not name the compressor ("new clearance and oil-injection design" suggests a screw, not stated), so no type is assigned. Annual AEER 9–12 is a seasonal claim, not a rating point.产品页未写容量和额定工况,也未写明压缩机类型("全新的间隙与喷油设计"像螺杆,但未写明),因此不分类型。全年 AEER 9–12 是全年能效说法,不是额定点。 |
| Company and line公司与产品 | Rated kW额定 kW | Chilled water supply / return °C冷冻水供 / 回水 °C | Condenser water in °C冷却水进水 °C | Efficiency at rating额定能效 | Input kW输入功率 kW | Part load部分负荷 | Max supply water °C最高供水 °C | Free cooling (vendor wording)自然冷却(厂商原文) | Refrigerant制冷剂 | Compressor压缩机 | Footprint L × W mm占地 长 × 宽 mm | Notes说明 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Dunham-Bush DCLC-D Hercules | family 1,055–10,550系列 1,055–10,550 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | not stated未披露 | dual-stage centrifugal双级离心 | not stated未披露 | Global product page: 300–3,000 RT (1,055–10,550 kW as printed); "Green Refrigerants" names no refrigerant. The page does not state the bearing or lubrication, so the line is not drawn on the charts; an oil-lubricated design is likely from DB China's DCLCDX two-stage centrifugal (same 300–3,000 RT range), whose page states sliding bearings and a VFD oil pump (that page is http only, so it is not cited as a public source).全球产品页:300–3,000 冷吨(原文 1,055–10,550 kW);"环保冷媒"未写明制冷剂。页面未写轴承和润滑方式,因此不在图中;可能为油润滑,依据是顿汉布什中国 DCLCDX 两级离心机(同为 300–3,000 冷吨),其页面写明滑动轴承和变频油泵(该页仅有 http,不作为公开来源)。 |