Delta Electronics InfraSuite CoolDoor D30 / D50 | Active (fans)主动式(带风机) | up to 50 kW最高 50 kW “Conditions for D50 rated capacity at return air: 50°C, Inlet water 12°C and outlet water 20°C” | 12 / 20 | 50 / — | Some conditions stated写明部分工况 | 4 EC fans4 台 EC 风机 | 345 mm345 mm | D50: 50 kW at 50 °C return air with 12 °C water in and 20 °C out (D30: 30 kW at 42 °C); Delta states that water above 12 °C requires derating. Air leaving not stated.D50:回风 50 °C、进水 12 °C、出水 20 °C 时 50 kW(D30:42 °C 时 30 kW);台达说明进水高于 12 °C 需降额。未写出风温度。 |
|---|
Lenovo ThinkSystem Rear Door Heat eXchanger V2 | Passive被动式 | up to 45 kW最高 45 kW “remove up to 35kW (42U) and 45kW (48U) into” | 16 / — | room 25室温 25 | Some conditions stated写明部分工况 | None: relies on the servers' fans无:依靠服务器风扇 | 129 mm129 mm | Up to 35 kW (42U) or 45 kW (48U) into 16 °C water at 25 °C ambient (Lenovo rack guide LP1498, May 2026). The product page asks for 18 or 22 °C ±1 °C water by ASHRAE room class and shows a curve, not a single rating.在 16 °C 水、25 °C 环境下最高 35 kW(42U)或 45 kW(48U)(Lenovo 机柜指南 LP1498,2026 年 5 月)。产品页按 ASHRAE 机房等级要求 18 或 22 °C ±1 °C 供水,并以曲线而非单一额定值表示。 Lenovo product pageLenovo 产品页 |
|---|
Motivair (Schneider Electric) ChilledDoor | Active (fans)主动式(带风机) | family 12–75 kW系列 12–75 kW “Nominal Cooling Capacity (kW)* 12 30 45 55 65 70 70 70 75” | 12.8–18.3 / — | room 23.9室温 23.9 | Some conditions stated写明部分工况 | 3–6 EC centrifugal fans, hot-swappable; up to 504–3,000 W3–6 台 EC 离心风机,可热插拔;最高 504–3,000 W | ○not stated未披露 | Rated at a 75 °F (23.9 °C) room, 35% RH and 55–65 °F (12.8–18.3 °C) supply water; air entering the door and water leaving it are not stated.额定条件为 75 °F(23.9 °C)室温、35% 相对湿度、55–65 °F(12.8–18.3 °C)供水;未写进门空气温度和出水温度。 |
|---|
nVent (Schroff) RackChiller RDHX PRO | Active (fans)主动式(带风机) | up to 78 kW最高 78 kW “78 kW @ 14°C supply water” | 14 / — | ○not stated未披露 | Some conditions stated写明部分工况 | 12 brushless DC axial fans, 1,800 W12 台无刷直流轴流风机,1,800 W | 281 mm with fans含风机 281 mm | 78 kW at 14 °C supply water with 24 °C "air supply", 44 kW at 24 °C water with 27 °C "air supply"; 6.0 m³/h water, 10,000 m³/h air; propylene glycol up to 35%. Air entering the door and water leaving are not stated. nVent datasheet read from a distributor-hosted copy.14 °C 供水、“供风” 24 °C 时 78 kW;24 °C 供水、“供风” 27 °C 时 44 kW;水量 6.0 m³/h,风量 10,000 m³/h;丙二醇最高 35%。未写进门空气温度和出水温度。nVent 数据表读自经销商托管的副本。 Table read as labels followed by values, in order.表格按“先标签、后数值”的顺序读取。 |
|---|
OptiCool Technologies Rear Door Heat Exchangers CDS-30 / 60 / 120 (refrigerant) | Active (fans)主动式(带风机) | up to 120 kW最高 120 kW “extracting up to 120 kW of heat per rack” | ○not stated未披露 | ○not stated未披露 | No water or air temperatures for the rating未写额定点的水温和气温 | Rear-door fans (count not stated); up to 396–3,834 W后门风机(未写台数);最高 396–3,834 W | 8.75 in including transition kit含过渡件 8.75 英寸 | Two-phase refrigerant door, 30, 60 or 120 kW, with no rating conditions; the refrigerant and its temperatures are not stated.两相制冷剂背板,30、60 或 120 kW,未写额定工况;未写制冷剂及其温度。 |
|---|
Rittal Rear Door Heat Exchanger | Active (fans)主动式(带风机) | up to 80 kW最高 80 kW “80 kW at 13,500 m³/h and 260 mm depth” | ○not stated未披露 | ○not stated未披露 | No water or air temperatures for the rating未写额定点的水温和气温 | Redundant fans (count not stated)冗余风机(未写台数) | 260 mm260 mm | 80 kW at 13,500 m³/h on Rittal's international page, but 70 kW in its US flyer and guide; no water or air temperatures. OCP Open Rack v3.Rittal 国际网页写 13,500 m³/h 时 80 kW,美国传单和指南写 70 kW;未写水温和气温。适用 OCP Open Rack v3。 Rittal US flyer (70 kW)Rittal 美国传单(70 kW) |
|---|
Stulz CyberRack Active Rear Door (2026 page) | Active (fans)主动式(带风机) | up to 49 kW最高 49 kW “Cooling capacity (kW): 49” | ○not stated未披露 | ○not stated未披露 | No water or air temperatures for the rating未写额定点的水温和气温 | EC fansEC 风机 | 274 mm274 mm | 49 kW, 6,200 m³/h and five fans, with no water or air temperatures. An earlier Stulz brochure (RBW C0, below) states conditions; it is not known whether the 49 kW follows them.49 kW、6,200 m³/h、5 台风机,未写水温和气温。较早的 Stulz 样本(RBW C0,见下行)写明了工况;不知 49 kW 是否沿用。 |
|---|
Stulz CyberRack RBW C0 (earlier brochure) | Active (fans)主动式(带风机) | up to 32.3 kW最高 32.3 kW “Cooling capacity1 kW 18.8 32.3” | 14 / 19 | 40 / — | Some conditions stated写明部分工况 | 5 fans, 0.80 kW5 台风机,0.80 kW | 330 mm330 mm | 32.3 kW with 40 °C air entering (20% RH) and water 14 °C in, 19 °C out, at 30 Pa external pressure; air leaving not stated. Brochure version mark "V1.1 05-18".进风 40 °C(相对湿度 20%)、进水 14 °C、出水 19 °C、外部静压 30 Pa 时 32.3 kW;未写出风温度。样本版本标记“V1.1 05-18”。 |
|---|
Supermicro Rear Door Heat Exchanger (DCBBS) | Active (fans)主动式(带风机) | up to 120 kW最高 120 kW “Cooling Capacity Up to 120 kW Up to 100 kW Up to 80 kW” | ○not stated未披露 | ○not stated未披露 | No water or air temperatures for the rating未写额定点的水温和气温 | By model: 6 fans, up to 3.6 kW (120 kW model); 12 fans, up to 5 kW (100 kW); 5 fans, up to 2.1 kW (80 kW); smaller models and a fan-door-only unit also listed按型号:6 台风机、最高 3.6 kW(120 kW 型号);12 台、最高 5 kW(100 kW);5 台、最高 2.1 kW(80 kW);另列有较小型号和仅风机门 | Varies by model因型号而异 | Up to 120 kW for the top model, with no water or air temperatures, flow or fluid. MGX, EIA and ORv3 racks.最高型号最高 120 kW,未写水温、气温、流量和介质。适用于 MGX、EIA 和 ORv3 机柜。 |
|---|
USystems (Legrand) ColdLogik CL20 ProActive | Active (fans)主动式(带风机) | up to 93 kW最高 93 kW “93 Cooling Capacity - Maximum 5 Fan 6 Fan Maximum Duty kW 62” | 14 / 30 | 58 / 20 | Water in and out, air in and out stated写明进出水温和进出风温 | 5 or 6 backward-curved centrifugal fans5 或 6 台后弯离心风机 | 380 mm with frame含框架 380 mm | 6-fan model: 93 kW with 14 °C water in, 30 °C out, 58 °C air in and 20 °C air out; 80 kW at 18 °C water in (55 °C air in, 22 °C out, water out 32 °C); 74 kW at 21 °C (55 °C air in, 25 °C out, water out 34 °C). Air-in temperature also changes between points. Figures are "for illustration purposes".6 风机型号:进水 14 °C、出水 30 °C、进风 58 °C、出风 20 °C 时 93 kW;进水 18 °C 时 80 kW(进风 55 °C、出风 22 °C、出水 32 °C);进水 21 °C 时 74 kW(进风 55 °C、出风 25 °C、出水 34 °C)。各工况的进风温度也不同。数据“仅供说明”。 Table layout: the 6-fan maximum (93) is printed above the 5-fan value (62).表格排版:6 风机最大值(93)印在 5 风机数值(62)上方。 |
|---|
USystems (Legrand) ColdLogik CL21 Smart Passive | Passive被动式 | up to 29 kW最高 29 kW “Max Duty kW 7 13 17 22 25 29” | 14 / 20 | 40 / — | Some conditions stated写明部分工况 | None: relies on the servers' fans无:依靠服务器风扇 | 198 mm198 mm | Up to 29 kW with 14 °C water in, 20 °C out and 40 °C air entering, at the highest server airflow shown (6,000 m³/h); 7 kW at 1,000 m³/h.进水 14 °C、出水 20 °C、进风 40 °C,在所列最大服务器风量(6,000 m³/h)下最高 29 kW;1,000 m³/h 时 7 kW。 Table header values (air on 40 °C, water in 14 °C) print above their labels.表头数值(进风 40 °C、进水 14 °C)印在其标签上方。 |
|---|
USystems (Legrand) ColdLogik CL23 HPC | Active (fans)主动式(带风机) | up to 204 kW最高 204 kW “Maximum Duty kW 204” | 14 / 20 | 65 / 15 | Water in and out, air in and out stated写明进出水温和进出风温 | 10 backward-curved centrifugal fans, 1,691 W at 100%10 台后弯离心风机,100% 时 1,691 W | 415 mm415 mm | 204 kW assumes 65 °C air entering and 15 °C leaving, with 14 °C water in, 20 °C out and 29.38 m³/h; Legrand shows the data "for illustration purposes". Such hot server exhaust is far from the OCP reference (45 °C). The datasheet also lists 177 kW (nominal) and 164 kW (efficient) at other conditions.204 kW 的前提是进风 65 °C、出风 15 °C,进水 14 °C、出水 20 °C、29.38 m³/h;Legrand 注明数据“仅供说明”。这么高的服务器排风温度远离 OCP 参考值(45 °C)。数据表另列额定 177 kW 和高效 164 kW,工况不同。 |
|---|
Vertiv CoolLoop RDHx (Liebert DCD) | Passive or active被动或主动 | family 35–80 kW系列 35–80 kW “Nomal cooling capacity [kW} … 35 600 / 800 2000 / 2200 11200 66 … 80 800 (750) 2000 / 2200 15300 90 1 1/4" 8.7 2900W” | ○not stated未披露 | ○not stated未披露 | No water or air temperatures for the rating未写额定点的水温和气温 | Passive door, or an active module (power 550–2,900 W at nominal capacity)被动门,或加装主动风机模块(额定容量时功率 550–2,900 W) | 120 mm passive (151 mm with swivel joint); 310 mm with active module被动 120 mm(含旋转接头 151 mm);加主动模块 310 mm | No water or air temperatures and no fluid behind the "nominal" capacities; a separate row gives 66–90 kW at 100 cfm per kW. ORv3 racks supported. "Nomal" is the datasheet's own typo.“额定”容量未写水温、气温和介质;另一行给出每 kW 100 cfm 时 66–90 kW。支持 ORv3 机柜。“Nomal”为数据表原文拼写错误。 Table read row by row: each row starts with the nominal kW of one model.表格按行读取:每行以一个型号的额定 kW 开头。 |
|---|