Do the parts inside the rack publish ratings that let warm water reach the chip?机柜内的部件是否公布了足以让温水到达芯片的额定值?

Over 3 years, the in-rack parts decide whether warm water reaches the chip.未来三年,机柜内部件决定暖水能否到达芯片。

Data as of 2026-10-13, reviewed monthly.数据截至 2026-10-13,每月复核。Condition: cold plates rated at stated conditions前提:冷板按写明的工况公布额定值

Interactive figure of a generic unit with its parts named. Requires JavaScript.通用机组互动图,标有各部件名称。需启用 JavaScript。

Cold coolant, supply低温冷却液,供液Warmed coolant, return升温后的冷却液,回液A generic unit, not to scale.通用机组,不按比例。

The in-rack liquid path of an AI serverAI 服务器的机柜内液路

How it works, and the sources工作原理和来源

Coolant from the CDU feeds the supply rail and passes through a hose and quick disconnects into the tray. Inside the cold plates, microchannel fins take up the chip heat, and the coolant returns the same way to the return rail. In this tray each lane runs two plates in series, so the coolant is already warmer in the tube between them. Other trays run plates in parallel, or plug straight into a blind-mate rail without hoses. The paired square rails with one port per server, the hoses from the server rear, the air bleeder and the drain valve follow Vertiv's CoolChip Fluid Network brochure and the OCP rack manifold white paper. That paper puts the bleed at the rail's high point, the drain at its low point and lists shut-off valves. The two lanes ending in a pair of rear couplings follow Envicool's Coolinside brochure, and the fin field under a cover follows CoolIT's Split-Flow brief and the OCP cold plate document. The rail spacing, exact tube routing, board layout, cut in the cover, fin count, rear power board and top coupling are illustrative.来自 CDU 的冷却液进入供液分水器,经软管和快接头进入托盘。冷板内的微通道翅片吸收芯片热量,升温后的冷却液按原路径流回回液分水器。这台托盘的每一路串联两块冷板,因此两板之间的管内冷却液已经升温。其他托盘采用并联冷板,或不用软管、直接盲插到分水器。成对的方形分水器、每台服务器一个接口、从托盘后部引出的软管、排气阀和排液阀,依据 Vertiv CoolChip Fluid Network 宣传册和 OCP 机柜分水器白皮书。该白皮书要求高点排气、低点排液,并列出截止阀。两路冷板汇到后部一对接头的布置依据英维克 Coolinside 宣传册,盖板下的翅片区依据 CoolIT Split-Flow 技术简报和 OCP 冷板文件。分水器间距、具体的管路走向、主板布置、盖板切口、翅片数量、后部电源板和顶部接头为示意。 Vertiv Fluid Network brochureVertiv Fluid Network 宣传册 · OCP rack manifold white paperOCP 机柜分水器白皮书 · Envicool Coolinside brochure英维克 Coolinside 宣传册 · CoolIT Split-Flow briefCoolIT Split-Flow 技术简报 · OCP cold plate requirementsOCP 冷板要求文件 · US patent 7751918 (plates in series)美国专利 7751918(冷板串联) · OCP ORv3 blind-mate manifoldOCP ORv3 盲插分水器规范

Quick disconnects are standardised: OCP UQD/UQDB v2.0.0 rated flow by size快接头已经标准化:OCP UQD/UQDB v2.0.0 各尺寸额定流量
UQD 02 2.27 L/minUQD 04 6.44 L/minUQD 06 11.36 L/minUQD 08 17.79 L/min
UQD 02 2.27 L/minUQD 04 6.44 L/minUQD 06 11.36 L/minUQD 08 17.79 L/min

OCP UQD/UQDB v2.0.0 sets per-size requirements: maximum operating pressure 6.89 bar (100 psi), minimum burst 20.68 bar, at least 5,000 coupling cycles, operating 5–65 °C. Its 'maximum flow' guidance is a 5 m/s velocity limit, which is the basis of Stäubli's flow figures, so they are not rated flows. Cv conditions: Stäubli states water at 998 kg/m³ and 1.08 cSt, flow direction socket to plug; Danfoss's flow chart states water at 60 °F, but its table does not assign that condition to each value. Values are not ranked. CPC and Parker datasheets could not be retrieved.OCP UQD/UQDB v2.0.0 按尺寸规定要求:最高工作压力 6.89 bar(100 psi),最低爆破压力 20.68 bar,至少 5,000 次插拔,工作温度 5–65 °C。其“最大流量”建议以 5 m/s 流速为限,这正是 Stäubli 流量数字的依据,所以那不是额定流量。Cv 条件:Stäubli 写明水、密度 998 kg/m³、黏度 1.08 cSt、流向从母端到公端;丹佛斯的流量图写明 60°F 的水,但其表格没有把该条件对应到每个数值。数值不做排名。CPC 和 Parker 的数据表无法获取。

Quick disconnects are standardised: OCP UQD/UQDB v2.0.0 rated flow by size快接头已经标准化:OCP UQD/UQDB v2.0.0 各尺寸额定流量

Table表格

Size尺寸OCP rated flow L/min (GPM)OCP 额定流量 L/min(GPM)OCP max fluid loss per cycle mLOCP 每次插拔最大漏液 mLDanfoss UQD: rated flow L/min, Cv, fluid loss cc, max working pressure丹佛斯 UQD:额定流量 L/min、Cv、漏液 cc、最高工作压力Stäubli UQD: flow at 5 m/s L/min, Cv, nominal diameterStäubli UQD:5 m/s 流量 L/min、Cv、公称通径
022.27 (0.6)0.022.1 · Cv 0.33 · 0.007 · 20 bar2.12 · Cv 0.37 · DN 3
046.44 (1.7)0.036.4 · Cv 1.37 · 0.01 · 16 bar8.48 · Cv 1.15 · DN 6
0611.36 (3.0)0.0411.4 · Cv 2.37 · 0.022 · 6.9 bar11.55 · Cv 2.52 · DN 7
0817.79 (4.7)0.0717.8 · Cv 5.32 · 0.03 · 6.9 bar23.56 · Cv 3.65 · DN 10

Sources来源

  1. OCP UQD/UQDB design specification v2.0.0OCP UQD/UQDB 设计规范 v2.0.0
  2. OCP UQD/UQDB v2.0.0OCP UQD/UQDB v2.0.0
  3. Danfoss Hansen UQD/UQDB丹佛斯 Hansen UQD/UQDB
  4. Stäubli UQD/UQDBStäubli UQD/UQDB
  5. Envicool UQD/UQDB (SUS316/316L housing, EPDM seal; no size table)英维克 UQD/UQDB(SUS316/316L 壳体,EPDM 密封;无尺寸表)
15kW

Cold-plate design CoolIT says it has validated for 45 °C warm-water systems (a design, not a shipping product)CoolIT 称已为 45 °C 温水系统验证的冷板设计(设计验证,不是量产产品)

Vendor claim厂商宣称CoolITCoolIT
0of 7

Cold-plate lines whose source gives thermal resistance and pressure drop at a stated flow, coolant and inlet temperature来源同时给出热阻和压降、并写明流量、冷却液和进液温度的冷板系列

From the engineering judgement摘自工程判断Judgement判断 Cold-plate table冷板表
6.89bar

Maximum operating pressure in OCP UQD/UQDB v2.0.0, which also sets at least 5,000 coupling cycles and 5–65 °C operationOCP UQD/UQDB v2.0.0 规定的最高工作压力;该规范还规定至少 5,000 次插拔、工作温度 5–65 °C

Open specification开放规范OCPOCP

Judgement判断

Over the next three years the in-rack parts decide whether warm water reaches the chip; CoolIT has already validated a 15 kW cold-plate design for 45 °C warm-water systems (a design, not a shipping product).

Quick disconnects are standardised by OCP's UQD/UQDB v2.0.0.

未来三年,机柜内部件决定暖水能否到达芯片;CoolIT 已经按 45 °C 暖水系统验证了 15 kW 的冷板设计(设计验证,不是量产产品)。

快接头已由 OCP UQD/UQDB v2.0.0 标准化。

Judgement by LC. Sources: LC 的判断。来源:[1] [2] [3]

Inside the rack, cold plates take heat off the chips, manifolds share the coolant across servers, and quick disconnects let a server leave the loop.在机柜里,冷板把热量从芯片带走,分水器把冷却液分配到各台服务器,快接头让服务器可以脱离回路。

What makers have said is coming厂商已宣布的下一步

Nov 20262026 年 11 月

Ecolab introduces a 3D TRASAR cooling platform with CoolIT cold plates at Supercomputing艺康在 Supercomputing 大会推出含 CoolIT 冷板的 3D TRASAR 冷却平台

Planned计划, announced 2026-07,2026-07 公布 source来源

Each stays a plan until a source confirms it happened. Passing the window does not prove shipment.在有来源确认发生之前,各项都只是计划。时间窗口过去并不代表已经出货。

Go deeper继续深入

Compare two or three自选两到三款比较

○ = not stated by the vendor. Values keep the vendor's own conditions; they are not a ranking. Choose "—" in the third box to compare two.○ = 厂商未标称。数值保留厂商自己的工况,不构成排名。第三个框选"—"即可只比较两款。

Three part types三类部件3

Rule: one card per part type, with what its sources state.规则:每类部件一张卡片,写明其来源说了什么。

Cold plates冷板

None of the cited cold-plate sources gives both thermal resistance and pressure drop at a stated flow, coolant and inlet temperature.所引用的冷板资料中,没有一份同时给出在给定流量、介质和进液温度下的热阻和压降。

7 rows7 行

Quick disconnects快接头

OCP UQD/UQDB v2.0.0 sets per-size requirements: maximum operating pressure 6.89 bar (100 psi), minimum burst 20.68 bar, at least 5,000 coupling cycles, operating 5–65 °C.OCP UQD/UQDB v2.0.0 按尺寸规定要求:最高工作压力 6.89 bar(100 psi),最低爆破压力 20.68 bar,至少 5,000 次插拔,工作温度 5–65 °C。

4 rows4 行

Rack manifolds机柜分水器

Manifolds are specified by rack, port count and connector rather than by heat load.分水器按机柜、接口数量和接头规格定义,而不是按热负荷。

4 rows4 行
The latest six product, contract and rule events最近六项产品、合同与法规事件6
  • Danfoss launches compact MQD/MQDB couplings: sizes 02–04, 2–6.8 L/min丹佛斯推出紧凑型 MQD/MQDB 快接头:02–04 尺寸,2–6.8 L/min Quick disconnects and manifolds快接头与分水器 source来源
  • Cooler Master reports supplying cold plates and manifolds for NVIDIA MGX racksCooler Master 报告为 NVIDIA MGX 机柜供应冷板和分水器 Cold plates冷板 source来源
  • Delta shows its NVIDIA Vera Rubin NVL72 cold plate at Computex台达在 Computex 展示 NVIDIA Vera Rubin NVL72 冷板 Cold plates冷板 source来源
  • CoolIT validates a 15 kW single-phase cold-plate design for 45 °C warm-water systems (a design, not a shipping product)CoolIT 验证面向 45 °C 暖水系统的 15 kW 单相冷板设计(设计验证,不是量产产品) Cold plates冷板 source来源
  • OCP's single-phase direct-to-chip cold plate test specification v1.0.0 takes effectOCP 单相直接芯片冷板测试规范 v1.0.0 生效 Cold plates冷板 source来源
  • OCP's combined UQD/UQDB design specification v2.0.0 takes effectOCP 合并版 UQD/UQDB 设计规范 v2.0.0 生效 Quick disconnects and manifolds快接头与分水器 source来源

A date marks an event that happened; the plans are shown above with their windows. The full six-year roadmap is in the next rows.有日期的是已发生的事件;计划及其时间窗口见上文。完整六年路线图在下面。

Company news: acquisitions, factories and funding公司动态:收购、工厂和融资5
  • Daikin Applied announces the acquisition of negative-pressure cooling specialist Chilldyne大金应用宣布收购负压液冷专业公司 Chilldyne Ownership and factories收购与工厂 source来源
  • CoolIT opens its Starfield factory (112,000 ft²) for cold plates through CDUsCoolIT 启用 Starfield 工厂(11.2 万平方英尺),生产从冷板到 CDU 的产品 Ownership and factories收购与工厂 source来源
  • Eaton completes the Boyd Thermal acquisition伊顿完成收购 Boyd 热管理业务 Ownership and factories收购与工厂 source来源
  • Vertiv announces the acquisition of Strategic Thermal Labs for cold-plate design维谛宣布收购 Strategic Thermal Labs,加强冷板设计 Ownership and factories收购与工厂 source来源
  • Ecolab completes the CoolIT acquisition (about USD 4.75 billion)艺康完成收购 CoolIT(约 47.5 亿美元) Ownership and factories收购与工厂 source来源
Full roadmap, makers and owners, and the method完整路线图、厂商与所有者、方法23 events23 个事件

Roadmap, 2023 Q4 – 2029 Q3路线图,2023 年第四季度至 2029 年第三季度

Dated events from official sources. Planned events show the window the source states; passing the window does not prove shipment. No future model is inferred.来自官方来源的有日期事件。计划事件显示来源给出的时间窗口;窗口过去并不代表已经出货。不推测未来型号。

Cold plates冷板

  1. May 20242024 年 5 月 CoolIT launches OMNI all-metal cold plates: over 1,500 W processor TDP and over 300 W/cm² heat fluxCoolIT 发布 OMNI 全金属冷板:处理器 TDP 超过 1,500 W,热流密度超过 300 W/cm²
  2. Sep 20242024 年 9 月 Envicool's cold plates, UQD connectors and rack manifolds pass Intel qualification英维克的冷板、UQD 快接头和机柜分水器通过英特尔认证
  3. Mar 20252025 年 3 月 CoolIT tests a 4,000 W single-phase cold-plate design: over 97% heat capture at 6 L/min; thermal resistance below 0.009 °C/W stated separatelyCoolIT 测试 4,000 W 单相冷板设计:6 L/min 时热量捕获率超过 97%;另行给出热阻低于 0.009 °C/W
  4. Sep 20252025 年 9 月 Schneider makes the Motivair portfolio, including Dynamic Cold Plates, available worldwide施耐德在全球推出 Motivair 产品组合,包括 Dynamic Cold Plates
  5. Nov 20252025 年 11 月 Envicool shows a pumped two-phase cold-plate system英维克展示泵驱两相冷板系统
  6. May 20262026 年 5 月 Cooler Master reports supplying cold plates and manifolds for NVIDIA MGX racksCooler Master 报告为 NVIDIA MGX 机柜供应冷板和分水器
  7. Jun 20262026 年 6 月 Delta shows its NVIDIA Vera Rubin NVL72 cold plate at Computex台达在 Computex 展示 NVIDIA Vera Rubin NVL72 冷板
  8. Jun 20262026 年 6 月 CoolIT validates a 15 kW single-phase cold-plate design for 45 °C warm-water systems (a design, not a shipping product)CoolIT 验证面向 45 °C 暖水系统的 15 kW 单相冷板设计(设计验证,不是量产产品)
  9. Sep 20262026 年 9 月 OCP's single-phase direct-to-chip cold plate test specification v1.0.0 takes effectOCP 单相直接芯片冷板测试规范 v1.0.0 生效
  10. Target Nov 2026目标 2026 年 11 月 Ecolab introduces a 3D TRASAR cooling platform with CoolIT cold plates at Supercomputing艺康在 Supercomputing 大会推出含 CoolIT 冷板的 3D TRASAR 冷却平台 announced Jul 20262026 年 7 月公布 planned计划

Quick disconnects and manifolds快接头与分水器

  1. Feb 20242024 年 2 月 Danfoss introduces UQD couplings for data-center liquid cooling in four sizes丹佛斯推出四种尺寸的数据中心液冷 UQD 快接头
  2. Apr 20242024 年 4 月 OCP's ORv3 blind-mate manifold specification, revision 1.0, is dated April 2024OCP ORv3 盲插分水器规范 1.0 版的文件日期为 2024 年 4 月
  3. Oct 20242024 年 10 月 Vertiv launches the CoolChip Fluid Network rack manifold维谛发布 CoolChip Fluid Network 机柜分水器
  4. May 20252025 年 5 月 Auras shows an AI rack manifold and an AI building manifold at Computex双鸿在 Computex 展示 AI 机柜分水器和 AI 建筑分水器
  5. Jul 20252025 年 7 月 CPC introduces Everis UQD06 connectors with a 3/8-inch flow pathCPC 推出 Everis UQD06 快接头,流道 3/8 英寸
  6. Aug 20252025 年 8 月 Danfoss launches UQDB08, completing its blind-mate range (sizes 02 to 08)丹佛斯推出 UQDB08,盲插系列补齐 02 至 08 四种尺寸
  7. Dec 20252025 年 12 月 Danfoss launches compact MQD/MQDB couplings: sizes 02–04, 2–6.8 L/min丹佛斯推出紧凑型 MQD/MQDB 快接头:02–04 尺寸,2–6.8 L/min
  8. Sep 20262026 年 9 月 OCP's combined UQD/UQDB design specification v2.0.0 takes effectOCP 合并版 UQD/UQDB 设计规范 v2.0.0 生效

Ownership and factories收购与工厂

  1. Nov 20252025 年 11 月 Daikin Applied announces the acquisition of negative-pressure cooling specialist Chilldyne大金应用宣布收购负压液冷专业公司 Chilldyne
  2. Dec 20252025 年 12 月 CoolIT opens its Starfield factory (112,000 ft²) for cold plates through CDUsCoolIT 启用 Starfield 工厂(11.2 万平方英尺),生产从冷板到 CDU 的产品
  3. Mar 20262026 年 3 月 Eaton completes the Boyd Thermal acquisition伊顿完成收购 Boyd 热管理业务
  4. Apr 20262026 年 4 月 Vertiv announces the acquisition of Strategic Thermal Labs for cold-plate design维谛宣布收购 Strategic Thermal Labs,加强冷板设计
  5. Jul 20262026 年 7 月 Ecolab completes the CoolIT acquisition (about USD 4.75 billion)艺康完成收购 CoolIT(约 47.5 亿美元)

Makers and owners厂商与所有者

Listed companies behind the products on this page: 本页产品背后的上市公司:VertivVertiv, Schneider ElectricSchneider Electric, nVentnVent, Envicool英维克, Delta Electronics台达电子, DaikinDaikin. Other makers: 其他厂商:CoolIT (owned by Ecolab since 2026-072026 年 7 月起归属艺康); Boyd Thermal (owned by Eaton since 2026-032026 年 3 月起归属伊顿); Cooler Master (private非上市); Stäubli (private非上市); Danfoss (private非上市); CPC (Dover) (part of Dover; not in this registryDover 旗下;不在本名单中); Parker (listed in New York; not in this registry纽约上市;不在本名单中). See the value-chain map查看产业链地图 · CDU deep diveCDU 深度分析

Method方法

Specifications come from each vendor’s datasheet, brochure or product page and the OCP specification; each source was extracted by two different models and ruled against the saved text. Events come from vendor and OCP pages; each was checked by script on the page and by an independent model. OCP's cold-plate test specification: https://www.opencompute.org/wp-content/uploads/2026/10/OCP-Cold-Plate-Test-Specification-V1.0.0.pdf. Evidence cut-off 2026-10-13. Personal research, not investment advice.规格来自各厂商的数据表、样本或产品页以及 OCP 规范;每个来源由两个不同模型分别提取,并对照保存的原文裁定。事件来自厂商和 OCP 页面,每条都经脚本在原页面核对并由独立模型复核。OCP 冷板测试规范:https://www.opencompute.org/wp-content/uploads/2026/10/OCP-Cold-Plate-Test-Specification-V1.0.0.pdf。证据截止 2026-10-13。个人研究,不构成投资建议。

Database view: cold plates, quick disconnects and manifolds数据库视图:冷板、快接头与分水器15 rows15 行
Showing显示 15

○ = not stated by the vendor (explained once here, not repeated in words in each cell).○ = 厂商未标称(只在此说明一次,不在每格重复文字)。

Cold plates: what the vendors state冷板:厂商写了什么

None of the cited cold-plate sources gives both thermal resistance and pressure drop at a stated flow, coolant and inlet temperature. CoolIT's published test results are the clearest numbers: a 4,000 W test vehicle with over 97% heat capture at 6 L/min and, stated separately, thermal resistance below 0.009 °C/W; and a 15 kW design validated for 45 °C warm-water systems.所引用的冷板资料中,没有一份同时给出在给定流量、介质和进液温度下的热阻和压降。CoolIT 公布的测试结果数字最清楚:4,000 W 测试件在 6 L/min 时热量捕获率超过 97%,另行给出热阻低于 0.009 °C/W;以及按 45 °C 暖水系统验证的 15 kW 设计。

Company and line公司与产品What the source states来源写明的内容Coolant and materials介质与材料
Envicool · Coolinside CPU/GPU cold plates英维克 · Coolinside CPU/GPU 冷板heat flux up to 100 W/cm² with whole-plate pressure drop below 30 kPa (no flow or inlet temperature stated)热流密度最高 100 W/cm²,整板压降低于 30 kPa(未写流量或进液温度)not stated未披露
Chilldyne (Daikin Applied) · negative-pressure cold platesChilldyne(大金应用)· 负压冷板“Supports loads up to 2000W” (conditions not stated)“支持最高 2000 W 负载”(未写工况)water, negative-pressure loop水,负压回路
Delta · AI server cold plate loop台达 · AI 服务器冷板回路“Power Consumption: 3100W” (as printed; not stated as cooling capacity)“Power Consumption: 3100W”(按原文;未说明是冷却能力)flexible copper tube柔性铜管
CoolIT (Ecolab) · OMNI all-metal cold platesCoolIT(艺康)· OMNI 全金属冷板“CoolIT’s coldplates typically show upwards of 60% lower thermal resistance than standard coldplate designs” (general claim for CoolIT cold plates); the brief also plots OMNI thermal resistance against flow (0.50–1.50 L/min) without readable values or inlet temperature“CoolIT 冷板的热阻通常比标准冷板低 60% 以上”(针对 CoolIT 冷板的总体说法);技术简报另画出 OMNI 热阻随流量(0.50–1.50 L/min)的曲线,没有可读数值和进液温度all-metal全金属
Boyd (Eaton) · custom direct-to-chip cold platesBoyd(伊顿)· 定制直接芯片冷板no performance figures; every plate 100% leak and flow tested before shipment无性能数字;每块冷板出厂前 100% 做泄漏和流量测试aluminium, copper, stainless steel; deionized water or water-glycol铝、铜、不锈钢;去离子水或水与二醇的混合液(原文未指定二醇种类)
Strategic Thermal Labs (Vertiv) · CP-BISStrategic Thermal Labs(维谛)· CP-BISno thermal rating; leak-proof operation up to 2,068 kPa (300 psi) operating pressure无热性能额定值;在最高 2,068 kPa(300 psi)工作压力下不泄漏all-metal brazed, or thermoplastic with O-ring全金属钎焊,或热塑性加 O 型圈
Cooler Master · GPU/CPU cold-plate kitCooler Master · GPU/CPU 冷板套件no performance figures; integrated leak detection无性能数字;集成漏液检测not stated未披露

Quick disconnects: vendor tables against the OCP specification快接头:厂商数据与 OCP 规范对照

OCP UQD/UQDB v2.0.0 sets per-size requirements: maximum operating pressure 6.89 bar (100 psi), minimum burst 20.68 bar, at least 5,000 coupling cycles, operating 5–65 °C. Its 'maximum flow' guidance is a 5 m/s velocity limit, which is the basis of Stäubli's flow figures, so they are not rated flows. Cv conditions: Stäubli states water at 998 kg/m³ and 1.08 cSt, flow direction socket to plug; Danfoss's flow chart states water at 60 °F, but its table does not assign that condition to each value. Values are not ranked. CPC and Parker datasheets could not be retrieved.OCP UQD/UQDB v2.0.0 按尺寸规定要求:最高工作压力 6.89 bar(100 psi),最低爆破压力 20.68 bar,至少 5,000 次插拔,工作温度 5–65 °C。其“最大流量”建议以 5 m/s 流速为限,这正是 Stäubli 流量数字的依据,所以那不是额定流量。Cv 条件:Stäubli 写明水、密度 998 kg/m³、黏度 1.08 cSt、流向从母端到公端;丹佛斯的流量图写明 60°F 的水,但其表格没有把该条件对应到每个数值。数值不做排名。CPC 和 Parker 的数据表无法获取。

Size尺寸OCP rated flow L/min (GPM)OCP 额定流量 L/min(GPM)OCP max fluid loss per cycle mLOCP 每次插拔最大漏液 mLDanfoss UQD: rated flow L/min, Cv, fluid loss cc, max working pressure丹佛斯 UQD:额定流量 L/min、Cv、漏液 cc、最高工作压力Stäubli UQD: flow at 5 m/s L/min, Cv, nominal diameterStäubli UQD:5 m/s 流量 L/min、Cv、公称通径
022.27 (0.6)0.022.1 · Cv 0.33 · 0.007 · 20 bar2.12 · Cv 0.37 · DN 3
046.44 (1.7)0.036.4 · Cv 1.37 · 0.01 · 16 bar8.48 · Cv 1.15 · DN 6
0611.36 (3.0)0.0411.4 · Cv 2.37 · 0.022 · 6.9 bar11.55 · Cv 2.52 · DN 7
0817.79 (4.7)0.0717.8 · Cv 5.32 · 0.03 · 6.9 bar23.56 · Cv 3.65 · DN 10

Sources: 来源:OCP UQD/UQDB v2.0.0OCP UQD/UQDB v2.0.0 · Danfoss Hansen UQD/UQDB丹佛斯 Hansen UQD/UQDB · Stäubli UQD/UQDBStäubli UQD/UQDB · Envicool UQD/UQDB (SUS316/316L housing, EPDM seal; no size table)英维克 UQD/UQDB(SUS316/316L 壳体,EPDM 密封;无尺寸表)

Rack manifolds机柜分水器

Manifolds are specified by rack, port count and connector rather than by heat load.分水器按机柜、接口数量和接头规格定义,而不是按热负荷。

Company and line公司与产品What the source states来源写明的内容
Vertiv · CoolChip Fluid Network (RM1xx)维谛 · CoolChip Fluid Network(RM1xx)36, 42 or 48 ports; coupling ID 3, 6 or 9 mm; max operating pressure 8 bar (116 psi); 304 stainless steel; 42U–52U racks36、42 或 48 个接口;接头内径 3、6 或 9 mm;最高工作压力 8 bar(116 psi);304 不锈钢;42U–52U 机柜
CoolIT (Ecolab) · rack manifolds for EIA, ORV3 and MGXCoolIT(艺康)· 适配 EIA、ORV3、MGX 的机柜分水器42–52 connection points; blind-mate options; FD83 TCS connection; treated stainless steel42–52 个连接点;可选盲插;FD83 二次侧接口;处理过的不锈钢
nVent · RackChiller rack manifold RCM42001nVent · RackChiller 机柜分水器 RCM42001FD83 supply and return; ORB-6 ports; 38 × 38 mm stainless tube; racks above 45UFD83 供回水接口;ORB-6 接口;38 × 38 mm 不锈钢管;45U 以上机柜
Envicool · Coolinside MDU030S / MDU030D英维克 · Coolinside MDU030S / MDU030DSUS304 and SUS316L listed by configuration; several section sizes listed按配置列出 SUS304 和 SUS316L;列出多种截面尺寸